WARNING
To prevent component damage or electric shock, avoid touching any
component or any part of the circuitry while the equipment is operating.
Do not place heavy loads on associated system cables or maneuver
them in a manner which may expose personnel or equipment to current.
Do not connect system cables when the terminals are wet or damp. Do
not disconnect cables under load.
Pour éviter des dommages aux composantes ou de choc électrique,
évitez de toucher tout composant ou toute partie du circuit tandis que
l'équipement est en marche. Ne placez pas de lourdes charges sur les
câbles du système associés ou les manœuvres d'une manière qui peut
exposer le personnel ou les équipements actuels. Ne pas brancher les
câbles du système lorsque les bornes sont mouillées ou humides. Ne
pas déconnecter les câbles sous charge.
16.0 MAINTENANCE
Please review this manual fully before beginning work on the CCB series
product. Follow all safety guidelines and warnings.
1. Perform visual, electrical and mechanical inspections on a regular
basis. The environment and frequency of use should determine
Standard Design
1.0 CCB Series
1.1 CCB_04
4 String Combiner Box (02-04 Strings)
1.2 CCB_10
10 String Combiner Box (05-10 Strings)
1.3 CCB_16
16 String Combiner Box (11-16 Strings)
1.4 CCB_20
20 String Combiner Box (17-20 Strings)
1.5 CCB_04 DS 4 String Combiner Box w/ Integral Disconnect Switch (02-04 Strings)
1.6 CCB_10 DS 10 String Combiner Box w/ Integral Disconnect Switch (05-10 Strings)
1.7 CCB_16 DS 16 String Combiner Box w/ Integral Disconnect Switch (11-16 Strings)
1.8 CCB_20 DS 20 String Combiner Box w/ Integral Disconnect Switch (17-20 Strings)
* For fiberglass only (600/1000V); consult factory for additional information.
Standard Design
1.0 CCB Series
1.9 CCB_04
4 String Combiner Box (02-04 Strings)
1.10 CCB_08
8 String Combiner Box (05-08 Strings)
1.11 CCB_12
12 String Combiner Box (09-12 Strings)
4 String Combiner Box w/ Integral Disconnect Switch
1.12 CCB_04 DS
(02-04 Strings)
8 String Combiner Box w/ Integral Disconnect Switch
1.13 CCB_08 DS
(05-08 Strings)
12 String Combiner Box w/ Integral Disconnect Switch
1.14 CCB_12 DS
(09-12 Strings)
* For fiberglass only (600/1000V); consult factory for additional information.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not
guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection herewith.
All manuals and user guides at all-guides.com
AVERTISSEMENT
Description
Table 1 - Electrical and Mechanical Ratings, Series 1.0
Description
Table 2 - Electrical and Mechanical Ratings, Series 1.0
Eaton's Crouse-Hinds Business
1201 Wolf Street, Syracuse, New York 13208 • U.S.A.
Copyright © 2015
this. However, it is recommended that checks be made every 6
months to inspect and re-torque all electrical connections per Table 1
(Extreme installation conditions may merit more frequent checks and
maintenance).
We recommend an Electrical Preventive Maintenance Program as
described in the National Fire Protection Association Bulletin NFPA No.
70B: Recommended Practice For Electrical Equipment Maintenance
(www.nfpa.org).
2. Visually check for undue heating evidenced by discoloration of wires or
other components, damaged parts, or leakage evidenced by water or
corrosion in the interior.
3. Mechanically check that all parts are properly assembled.
REPLACEMENT PARTS
Eaton's Crouse-Hinds Series Solar Combiner Boxes are designed
to provide years of performance. However, should the need for
replacement parts arise, they are available through your authorized
Eaton's Crouse-Hinds Division distributor. Assistance may also be
obtained through your local Eaton's Crouse-Hinds Division representative.
Replacement kits are available for any consumable parts.
Tech Spec
Max
Max
Current for
Voltage
Ambient
Fuse
Greatest
(VDC)
(°C)
Size
Number of
(A)
Strings
(A)
600/1000
50
30
96
600/1000
50
30
240
600/1000
50
30
384
600/1000
50
30
480
600/1000
50
30
96
600/1000
50
30
240
600/1000
50
30
384
600/1000
50
30
480
• Consult factory for special output conductor requirements.
Tech Spec
Max
Max
Current for
Voltage
Ambient
Fuse
Greatest
(VDC)
(°C)
Size
Number of
(A)
Strings
(A)
600/1000
50
60
192
600/1000
50
60
384
600/1000
50
60
576
600/1000
50
60
192
600/1000
50
60
384
600/1000
50
60
576
• Consult factory for special output conductor requirements.
Mech Spec * •
Max PV
Input Conductors
Output Conductors
Module
(Cu./Al.)
Short
Circuit
Wire Gauge
Torque
Wire Gauge
Current
Min.
(in-lbs)
(A)
19.2
300 MCM
19.2
350 MCM
19.2
600 MCM
CU 2-3
50
CU4-6
45
19.2
800 MCM
CU 8-14
35
19.2
300 MCM
AL 2-6
50
AL 8
40
19.2
350 MCM
19.2
600 MCM
19.2
800 MCM
Mech Spec * •
Max PV
Input Conductors
Output Conductors
Module
(Cu./Al.)
Short
Circuit
Wire Gauge
Torque
Wire Gauge
Current
Min.
(in-lbs)
(A)
38.4
350 MCM
38.4
500 MCM
38.4
800 MCM
#6 - 250
38.4
350 MCM
325
MCM
38.4
500 MCM
38.4
800 MCM
(Cu./Al.)
NEMA
Fiberglass
Rating
Dimensions
(inches)
Type
Torque
(in-lbs)
325
20x16x08 4X/4/3R
325
24x20x10 4X/4/3R
375
24x24x10 4X/4/3R
500
24x24x10 4X/4/3R
325
20x16x08 4X/4/3R
325
24x20x10 4X/4/3R
375
30x24x10 4X/4/3R
500
36x30x10 4X/4/3R
(Cu./Al.)
NEMA
Fiberglass
Rating
Dimensions
(inches)
Type
Torque
(in-lbs)
325
20x20x10 4X/4/3R
375
24x24x10 4X/4/3R
500
30x24x10 4X/4/3R
325
24x24x10 4X/4/3R
375
36x30x08 4X/4/3R
500
48x36x12 4X/4/3R
IF 1710
Revision 2
Revised 10/15
Supercedes 08/15