Recommended photovoltaic string
inputs for all fiberglass enclosures
and steel enclosures sizes 1-6 string
and 7-12 string
1"
1-1/4"
BOTTOM/RIGHT/LEFT SIDE VIEW
Recommended combined
conduit output for all size
enclosures
BOTTOM/RIGHT/LEFT SIDE VIEW
Recommended photovoltaic string inputs for
steel enclosures sizes 13-20 string and 20-24
string
1.00
Note: Combined output conduit not to exit top of enclosure. Ensure
adequate wire bend space is maintained per UL1741 and NEC Article
312. Ensure adequate wire bend space is maintained per UL1741.
Figure 1 - Conduit Entry Locations
be connected to the conduit before the enclosure. In lieu of a factory
supplied output lug, a lug rated for the appropriate voltage, current,
and conductor material, to be supplied and installed in the field, may
be used. Eaton's Crouse-Hinds Series NCGS Solar Cord Grips are
recommended for use with USE-2 and PV rated cable. Combined
output conduit not to exit top of enclosure.
6.3 INSTALL CONNECTOR
CAUTION
To ensure proper grounding, bonding between conduit connection is not
automatic and must be provided as a part of installation.
La liaison entre le cadre conduit n'est pas automatique et doit être
fournie dans le cadre de l'installation.
6.3.1 METALLIC CONDUIT
Place Myers hub through hole as shown in Figure 3 with the o-ring
on the outside of the enclosure. Screw on and tighten the locknut.
Next, screw on the grounding bushing, rotate to desired location
and tighten set screws. If ground hub configuration is used,
terminate ground wire to ground screw on locknut. If standard
configuration is used, screw on grounding bushing (Eaton's
Crouse-Hinds Series HGLL recommended). Rotate to desired
location, tighten set screw and terminate ground wire to ground
lug.
6.3.2 NON-METALLIC LT CONDUIT
Place connector through hole as shown in Figure 3 with the o-ring
on the outside of the enclosure. Screw on and tighten the locknut.
IF 1710 • 10/15
All manuals and user guides at all-guides.com
BOTTOM VIEW
1"
1"
BOTTOM VIEW
2.38
6.25
1.00
AVERTISSEMENT
Copyright © 2015, Eaton's Crouse-Hinds Division
*
*For metallic enclosures only
Non-Metallic Liquidtight
Solar Non-Metallic Cord
Grips
Figure 2 - Suitable Conduit Connectors
Figure 3 - Conduit Connector Exploded View
CAUTION
To ensure proper grounding, bonding between conduit connection is not
automatic and must be provided as a part of installation.
La liaison entre le cadre conduit n'est pas automatique et doit être
fournie dans le cadre de l'installation.
Screw insulated or plastic bushing onto connector threads to
protect conductors from damage. Grounding bushings are not used
with non-metallic conduit.
6.3.3 PVC CONDUIT
Place Eaton's Crouse-Hinds Series male adapter connector
(MA-NM recommended) through hole. Secure with steel locknut.
Grounding bushings are not used with PVC conduit.
7.0 BUS BAR
WARNING
To avoid personal injury, ensure ample time to cool. Bus bar may still be hot
while servicing.
Pour eviter dommages corporels, assurez-vous suffisamment de temps
pour refroidir. Barre de bus peut être encore chaude pendant l'entretien.
The positive and negative busbar should be torqued periodically to
ensure adequate connection. See Section 16.0 Maintenance and
Table 1 for torque values.
8.0 DISCONNECT SWITCH (OPTIONAL)
If no integral disconnect switch is provided, one must be utilized in
the PV system at time of installation and any conductor not opened
through disconnect switch must be grounded during installation. All
disconnects to be turned to the OFF position and locked out prior
to servicing.
†
†For metallic or non-metallic enclosures
AVERTISSEMENT
AVERTISSEMENT
Page 2