V-TAC VT-6605305 Manuel D'instructions page 31

Onduleur solaire avec affichage lcd et interrupteur dc -tri-phasé

Publicité

Les langues disponibles

Les langues disponibles

UV Volt
UV time
OV Volt
Run Param
Input password
0000
Run Param
OV time
UF Freq
UF time
ACUV Volt(phase volt)
184V
ACUV Time
0.20s
ACOV Volt(phase volt)
263V
ACOV Time
0.20s
ACUF Freqency
47.6Hz
ACUF Time
0.20s
ACOF Freqency
51.4Hz
ACOF Time
0.20s
Password is required when enter into
the interface of "Run Param". Get the
password from the supplier if
necessary. Set ACUV Volt, ACUV time
and others under the related
submenus, and then press "
"
" to modify, and finally press
"ENT" to confirm.