(2) The installation site must be well ventilated
and away from raindrops or direct sunlight.
(3) There must be enough pre-reserved space
around the installation site for convenient
disassemble of the inverter and air convection
(4) The ambient temperature of installation should be -25°C~60°C.
(5) The installation site should be away from electronic devices which can generate strong
electromagnetic interference.
(6) The inverter should be installed on firm and solid surface such as wall surface and metal
bracket.
(7) The installation surface should be vertical to the horizontal line.
(8) The installation should ensure that the inverter is reliably grounded, and the material of
grounded metal conductor should be consistent with the metal material reserved for the
grounding of the inverter.
Install the inverter vertically or backward ≤ 15° to facilitate heat dissipation.
Do not tilt the inverter forward, horizontal, upside down, over- backward, and roll when
install the inverter.
Do not open the cover of the inverter or replace any part as incomplete
inverter may cause electric shock and damag e the device during operation.
Figure 8 Installation space
Figure 9 Installation position