QUADRUPLE SYSTEM MULTI R.A. . MULTIZONE 80H
OOL / HEAT APA ITY SPE . FOR INDOOR UNITS
TO BE ABLE TO OPERATE SIMULTANEOUSLY
Whichever indoor units are installed, cooling and heating capacity
depends on how many and which indoor units are operating at that time.
ODEL :
RAM―80QH5
POSSIBLE
CO BINATIONS
CAPACITY RATING
TO OPERATE
(kW)(RANGE)
1.8
(1.00-2.50)
2.5
(1.00-2.80)
3.5
(1.00-4.00)
5.0
(1.00-5.60)
1.80+1.80
1.8+1.8
(1.50-4.10)
1.80+2.50
1.8+2.5
(1.50-4.50)
1.80+3.50
1.8+3.5
(1.50-5.80)
1.70+4.90
1.8+5.0
(1.50-7.20)
2.50+2.50
2.5+2.5
(1.50-5.60)
2.50+3.50
2.5+3.5
(1.50-6.60)
2.50+4.50
2.5+5.0
(1.50-7.60)
3.50+3.50
3.5+3.5
(1.50-7.60)
3.10+4.40
3.5+5.0
(1.50-8.00)
4.00+4.00
5.0+5.0
(1.50-8.20)
1.80+1.80
1.8+1.8
(1.50-4.00)
1.70+2.30
1.8+2.5
(1.50-4.50)
1.60+2.40
1.8+3.5
(1.50-5.50)
1.50+4.10
1.8+5.0
(1.50-6.20)
2.50+2.50
2.5+2.5
(1.50-5.50)
2.30+3.30
2.5+3.5
(1.50-6.20)
2.80+2.80
3.5+3.5
(1.50-6.20)
Two units
Each unit is connected to each compressor.
...
Two units
Two units are connected to one compressor.
...
All manuals and user guides at all-guides.com
OMBINATIONS
COOLING
OUTDOOR UNIT
POWER
CONSU PTION
(W)
1.80
560
(360-750)
2.50
780
(360-980)
3.50
1160
(360-1280)
5.00
1910
(360-2100)
1120
(640-1240)
1320
(640-1450)
1760
(640-1940)
1990
(640-2190)
1560
(640-1720)
1990
(640-2190)
2580
(640-2840)
2580
(640-2840)
2720
(640-2990)
2760
(640-3040)
1120
(640-1230)
1280
(640-1400)
1660
(640-1830)
1860
(640-2050)
1660
(640-1830)
1860
(640-2050)
1860
(640-2050)
- 14 -
CAPACITY RATING
A PARE
(kW)(RANGE)
(A)
230V
2.50
2.5
(1.10-3.20)
3.90
3.4
(1.10-4.70)
4.80
5.1
(1.10-5.80)
6.70
8.4
(1.10-7.60)
2.50+2.50
4.9
(1.50-5.50)
2.50+3.90
5.8
(1.50-7.00)
2.50+4.80
7.7
(1.50-8.40)
2.20+6.00
8.7
(1.50-9.00)
3.90+3.90
6.9
(1.50-8.60)
3.90+4.80
8.7
(1.50-9.60)
3.00+6.00
11.3
(1.50-9.90)
4.70+4.70
11.3
(1.50-10.30)
4.00+5.60
11.9
(1.50-10.60)
4.80+4.80
12.1
(1.50-10.60)
2.25+2.25
4.9
(1.50-5.20)
2.20+2.60
5.6
(1.50-5.50)
2.00+3.80
7.3
(1.50-6.40)
1.70+4.50
8.2
(1.50-6.80)
2.90+2.90
7.3
(1.50-6.40)
2.60+3.60
8.2
(1.50-6.80)
3.10+3.10
8.2
(1.50-6.80)
HEATING
OUTDOOR UNIT
POWER
A PARE
CONSU PTION (A)
(W)
230V
690
3.0
(320-970)
1100
4.8
(320-1280)
1380
6.1
(320-1750)
2070
9.1
(320-2170)
1380
6.1
(600-1520)
1770
7.8
(600-1950)
2150
9.4
(600-2380)
2850
12.5
(600-3150)
2160
9.5
(600-2390)
2690
11.8
(600-2960)
3200
14.1
(600-3520)
3200
14.1
(600-3520)
3300
14.5
(600-3630)
3300
14.5
(600-3630)
1280
5.6
(600-1480)
1360
6.0
(600-1600)
1580
6.9
(600-1740)
1930
8.5
(600-2120)
1580
6.9
(600-1740)
1930
8.5
(600-2120)
1930
8.5
(600-2120)

Publicité

loading