Connecting The Pdu - Tripp-Lite PDUMH15NET Manuel De L'utilisateur

Masquer les pouces Voir aussi pour PDUMH15NET:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation

Connecting the PDU

2-1
NEMA Adapter Connection (Optional -
PDUMH20HVNET Only): The
PDUMH20HVNET includes a plug adapter that
adds a NEMA L6-20P plug to the input power
cord. Use this adapter only if you will be
connecting the PDUMH20HVNET to a NEMA
L6-20R outlet. Insert the IEC 60320 C19
connector
of the adapter into the IEC 60320
A
C20 connector
of the input power cord.
B
Secure the connection with the retention bracket
by using the included bolts to fasten the two
C
halves of the bracket around the connection as
shown. Caution: To avoid the risk of electric
shock, ensure that the Neutral (L2) conductor
has been identified before connecting the PDU.
2-2
Input Power Cord Connection (Select
Models with Unattached Power Cords Only):
Insert the IEC 60320 C19 (PDUMH20HVNET)
or IEC 60320 C13 (PDUMH15HVNET)
connector
of the input power cord into the
A
IEC 60320 C20 (PDUMH20HVNET) or IEC
60320 C14 (PDUMH15HVNET) inlet
PDU. Connect the other end of the input power
cord
to a compatible source of AC power,
C
such as a UPS system, PDU or utility outlet.
The PDU should be provided with over-current
protection: PDUMH20HVNET should be
provided with a maximum 20A branch-rated
over-current protection device;
PDUMH15HVNET should be provided with a
maximum 15A branch-rated over-current
protection device.
Note: The AC power source should not share a circuit with a
heavy electrical load (such as an air conditioner or
refrigerator).
2-3
Connect Input Power Cord
(PDUMH15NET and PDUMH20NET):
Connect the input plug
of AC power, such as a UPS system, PDU or
utility outlet. The PDU should be provided with
over-current protection: PDUMH15NET with a
maximum 15A branch-rated protection device.
PDUMH20NET with a maximum 20A branch-
rated protection device.
17-10-354-932718.indb 4
continued
of the
B
to a compatible source
A
2-1
PDUMH15HVNET
88
C
2-2
PDUMH20HVNET
A
2-3
PDUMH15NET/PDUMH20NET
4
C
A
B
8 8
B
C
A
B
A
11/17/2017 8:38:14 AM

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pdumh20netPdumh15hvnetPdumh20hvnet

Table des Matières