Enocean/Knx Plug-In Modules; Enocean Components; Knx Components; Optional Accessories - AEREX geniovent.x 600 S Notice De Montage Et Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and operating instructions for geniovent.x 600 - 900 S
Notice de montage et mode d'emploi geniovent.x 600 - 900 S

12 EnOcean/KNX plug-in modules

12.1 EnOcean components

Install plug-in module in accordance with the accessory in-
structions.

12.2 KNX components

The installer level cannot be selected via KNX. Use the
commissioning software, the AIR@home APP or the
AIR@home web tool for this.
For parameters and possible functions → ac-
cessories instructions.

13 Optional accessories

13.1 Room air controls

RLS T1 SYS (item no. 0157.1643): Touchscreen control
panel for ventilation units with air@home control. Graphic,
high-resolution colour TFT display with easy-to-use, intuit-
ive menu navigation.
• For operation and configuration of various time pro-
grams, operating modes, ventilation levels, automatic
night cooling, flush mode etc. as well as to display status
information and alarm messages.
• Multiple-unit compatibility: up to 10 different
geniovent.x units with air@home control can be con-
trolled.
• Can be updated using a micro SD card.
• Preset language: German
Technical features
• Rated voltage: 12 V DC
• Colour: white similar to RAL 9010
• Material: Polystyrene, PVC-free
• W x H x D: 132 x 92 x 19 mm
• Type of installation: Surface-mounted
• Degree of protection: IP 00
EN
Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de
Only one RLS T1 SYS or one RLS G1 WS can be
connected! Two control panels cannot be run in
parallel.
For optional retrofitting, replacement and general explan-
ations of the RLS T1 SYS room air control → Installation
and operating instructions of the accessories at
www.aerex.de.

13.2 Electric preheating register

Available as an accessory for the (E) variants with enthalpy
heat exchanger. (G) variants with cross-counterflow heat
exchanger are fitted with an electric preheating register as
standard. This prevents the heat exchanger from icing over
at outside temperatures below 0 °C.*

13.3 Electric supplementary heat register

Used for supplementary heating of the supply air.*

13.4 External CO2 sensor

Additional sensor to register the external CO2 concentra-
tion in the air. An internal CO2 sensor is installed in all
units as standard. It is installed outside the ventilation unit.
Depending on the CO2 concentration, the ventilation unit
adapts the volumes of air to suit demand. If the CO2 con-
centration in the air improves, the speed of the ventilation
unit fans decreases. If the CO2 concentration deteriorates,
the speed of the ventilation unit fans increases.

13.5 External VOC sensor

Additional sensor to register the external air quality. An in-
ternal CO2 sensor is installed in all units as standard. It is
installed outside the ventilation unit. Depending on the air
quality, the ventilation unit adapts the volumes of air to
suit demand. If the air quality improves, the speed of the
ventilation unit fans decreases. If the air quality deterior-
ates, the speed of the ventilation unit fans increases.

13.6 Motion sensor (PIR)

When operating with a motion sensor, the unit must be
switched on. This activates the ventilation unit fans if there
are people in the room. If the `Manual´ operating mode is
selected, the unit runs in manual mode after movement is
registered. If the `Auto/time´ operating mode is selected,
the unit runs in sensor mode after movement is registered
(demand-controlled). The overrun time can be adjusted
(5...12...120 min).

13.7 Smoke gas switch

A smoke gas switch is a safety device for the early detec-
tion of the presence of smoke and for preventing it from
spreading within residential units through the ventilation
system. If required, the smoke gas switch switches off the
fans in the ventilation unit. Also observe the fire preven-
tion requirements.*
* If items marked with an * are ordered at the
same time, they are fitted in the unit in the factory
and arrive ready for use.

14 Spare parts

Only use original replacement filters.
Article no.
Article description
0093.1464
Replacement filter, outside air,
F7 900 S
0093.1465
Replacement filter, outside air,
M5 900 S
0093.1409.0001 Heat exchanger package, sens-
itive 900 S
0093.1427.0001 Heat exchanger package, en-
thalpy 900 S
0101.1431.9000 Control circuit board, cpl.,
KWL2GVX
0157.1366.0000 Temperature sensor, NTC 3.0m 1
0156.0179.0001 Radial fan, supply air/exhaust
air, geniovent.x 600 S
0156.0178.0000 Radial fan, supply air/exhaust
air, geniovent.x 900 S
0093.1303.0000 Condensate lift pump
0157.1428.0000 Preheating register, 1.5 kW,
600 S
0157.1392.0000 Preheating register, 2.5 kW,
900 S
0093.1408.0000 Shutter, cpl., 900 S
0157.1322.0000 Rotary drive, 26 Ncm, 230 VAC 1
0157.1376.0000 Mains filter (Schurter), AC filter
FSS2-65-4/3
0156.0193.0000 Bypass shutter servomotor
E093.1411.0000 Door, small, 900 S, cpl.
E093.1410.0000 Door, large, 900 S, cpl.
0157.1371.0000 Smoke gas switch
0157.1332.0000 CO2 sensor
0157.1331.0000 VOC sensor
E093.1467.0000 Connection area with spigot,
900 S (K3)
0043.0570
RB-ZF4 control panel

15 Service documentation

Model
Serial
number
Date
Work on the unit Name
Visual inspection
Quant-
of heat exchanger
ity
Outside air filter
(in
replacement
pieces)
Exhaust air filter
1
replacement
1
Model
Serial
1
number
Date
Work on the unit Name
1
Visual inspection
of heat exchanger
1
Outside air filter
replacement
Exhaust air filter
1
replacement
1
Company information
© Aerex HaustechnikSysteme GmbH. Translation of the
1
original operating instructions. Misprints, errors and tech-
1
nical changes are reserved. The brands, brand names and
protected trade marks that are referred to in this docu-
1
ment refer to their owners or their products.
1
1
1
1
7185.1234.0003_RLF.9_02.23_AS
1
1
1
1
1
1
Signature
Signature
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Geniovent.x 900 s

Table des Matières