STEP 12: Run the motor
Action
Power Up
Ensure:
•
Minimum and
Enter:
maximum speed
•
•
Accel and Decel
Enter:
rates
•
•
Motor nameplate
details
Ready to autotune
Autotune
The drive is able to perform either a stationary or a rotating autotune. The motor must be at
a standstill before any autotune is enabled and disconnected from the load for a rotating
autotune.
To perform an autotune:
•
•
•
•
•
Ready to run
Run
The drive is now ready to run the motor. Close the Run Forward or Run Reverse terminals
on Unidrive M100, M200 and M300 only.
Increasing and
Changing the selected Analog frequency reference (Speed Ref Potentiometer on M101 /
decreasing speed
M201) will increase and decrease the speed of the motor.
Stopping
To stop the motor by following the selected deceleration rate, open either the run forward or
run reverse terminal on Unidrive M100, M200 and M300 only. If the enable terminal is
opened while the motor is running, the drive output is immediately disabled and the motor
will coast to a stop.
Troubleshooting
When the drive detects a fault it will display an error code. To locate and solve all error codes, a 'Diagnostic Tool
(App)' is available on Microsoft, Android and iOS platform via the 'Apps' store on Smartphone / Tablet, search for
'Control Techniques diagnostics tool in the Apps store'.
Alternatively, please download the 'Diagnostic Tool (App)' from the Control Techniques 'App Center' or view the
diagnostics section in the Quick Start Guide available for download from the Control Techniques or Leroy Somer
website.
Unidrive M100/M101/M200/M201/M300 Step By Step Guide
Issue Number: 2
The drive displays: inh (Enable terminal(s) is open)
Minimum speed Pr 01 (Hz)
Maximum speed Pr 02 (Hz)
Acceleration rate Pr 03 (s/100 Hz)
Deceleration rate Pr 04 (s/100 Hz)
Motor rated current in Pr 06 (Amps)
Motor rated speed in Pr 07 (rpm / min
Motor rated voltage in Pr 08 (Volts)
Motor rated power factor in (cos
Set Pr 38 = 1 for a stationary autotune or set Pr 38 = 2 for a rotating autotune
Close the drive enable signal (apply +24 V to terminal 11 or terminal 31 and 34 on
Unidrive M300). The drive will display 'rdy'.
Give a Run command (apply +24 V to terminal 12 - Run forward or terminal 13 -
Run reverse on Unidrive M100, M200 and M300; press keypad Start button on M101
and M201). The display will flash 'tuning' while the drive is performing the autotune.
Wait for the drive to display 'inh' and for the motor to come to a standstill.
Remove the drive enable and run signal from the drive.