FRANÇAIS, page 152
-
-
-
-
EN
8. Diagnostics
ID
Description
3
Evaporator
temperature probe
alarm
4
Coldroom 2
temperature probe
alarm
5
Evaporator 2
temperature probe
alarm
6
Circuit 1 Suction
pressure probe
alarm
7
Circuit 1 condensing
pressure probe
alarm
8
Ambient
temperature probe
alarm
9
Suction
temperature probe
alarm
10
Discharge
temperature probe
alarm
11
Liquid temperature
probe alarm
132
BEST W R290
Cause
Value measured
Visual indication
outside the
only
operating ranges
Faulty or
disconnected
sensor
Value measured
Visual indication
outside the
only, evaporator
operating ranges
defrost carried out
due to Time-out
Faulty or
disconnected
sensor
Value measured
Visual indication
outside the
only, evaporator 2
operating ranges
defrost carried out
due to Time-out
Faulty or
disconnected
sensor
Value measured
If the Leak Function
outside the
is active, it causes
operating ranges
circuit 1 to stop,
otherwise only a
Faulty or
visual indication is
disconnected
given
sensor
Value measured
Visual indication
outside the
only
operating ranges
Faulty or
disconnected
sensor
Value measured
Visual indication
outside the
only. If the Floating
operating ranges
Condensing
function is enabled,
Faulty or
parameter EFC=1,
disconnected
this is disabled.
sensor
Value measured
Visual indication
outside the
only
operating ranges
Faulty or
disconnected
sensor
Value measured
Visual indication
outside the
only
operating ranges
Faulty or
disconnected
sensor
Value measured
Visual indication
outside the
only
operating ranges
Faulty or
disconnected
sensor
Impact
Resolution
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Check wiring and
integrity of the
probe and replace it
if necessary
Instruction manual
v. 00 | 9600-0033
Rev.
Reset
Relay
(*)
A
No
A
No
A
No
A
Yes
A
No
A
No
A
No
A
No
A
No