Maintenance
You must not try to repair the
JRG CleanLine Filter.
Backwashing the filter:
Ensure a sufficiently large drain line
after the drain pipe. At a primary pres-
sure of 1'600 kPa (16 bar) a discharge
rate of 1.25 l/s is to be expected.
For information regarding further
flushing rates at lower primary pres-
sure, see installation instructions.
7
Turn the hand wheel 8 clock-
wise, the LED 10 will light, until
8
water leaks from the drain pipe.
Now the first filter chamber is
flushed:
Flushing time 3-5 seconds.
Repeat this process until all eight filter
chambers are flushed. After the eighth filter
30
chamber the hand wheel palpably locks, the LED
10 goes out. The flushing process is complete.
If the filter is heavily soiled, we recom-
mend repeating the previously described
flushing process.
Make sure water stops leaking from the
drain pipe after completing the flushing.
If water is still leaking from the drain
pipe, fully repeat the above-described
flushing process.
After flushing, turn the month ring 7 to match
the current month (month digit pointing upwards).
This enables you to determine when the filter
was flushed last.
Malfunctions
In case of persistent problems, please
contact your local plumbers.