Mounting
Choose a mounting method (see right). Mount the control
interface in an accessible location.
1. Wall Mounting. Mount the control interface directly on
a wall, as shown, using screws (not included). When
mounting, provide sufficient space for connecting cables.
2. Rack Mounting. Place the unit in the LUT-19AV-1U AV rack
using screws (not included). The rack will hold up to four
units.
3. Conduit Mounting. If conduit is desired for wiring, the
LUT-5x10-ENC can be used to mount one unit.
Note: Contact closure output relays click audibly when
switching. Mount where this will not cause inconvenience.
2.50
3.75
Wiring Notes
• Refer to the system installation guide and Lutron job
drawings for power cable and data cable (control link) wiring
restrictions and limitations.
5.26
• Daisy-chain and T-tap wiring configurations are allowable.
• Use the wire connector required by local code.
1.06
• Control link wiring must not be run in the same raceway as
line voltage.
• The drain/shield wire must be maintained throughout the
control link. Do not connect the shield to earth/ground or
allow contact with the grounded wallbox.
• Do not connect high-voltage power to this unit. Improper
wiring can result in personal injury or damage to the control
or to other equipment.
QS Link Wire Sizes (check compatibility in your area)
QS Link Wiring Length
< 500 ft (< 153 m)
500 ft to 2000 ft
(153 m to 610 m)
2 QSE-IO Control Interface Installation Instructions
4.26
Wire Gauge
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
Data (terminals 3 and 4)
1 twisted, shielded pair
22 AWG (0.5 mm
)
2
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
Data (terminals 3 and 4)
1 twisted, shielded pair
22 AWG (0.5 mm
)
2
Mounting Diagrams
1
Wall
Control Interface
WARNING! Shock hazard. May result in
serious injury or death. Always turn off the
circuit breaker/MCB or remove main fuse from
power line before doing any work.
1. Turn power OFF. Turn the power
off at the circuit breaker/MCB (or
remove fuse).
2. Prepare the wires. Strip the
insulation from the wires so that
3/8 in (10 mm) of bare wire is
exposed.
LutronR Cable Part Number
)
2
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
)
2
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
2
LUT-19AV-1U
3
LUT-5x10-ENC
Wire Strip Length
0.375 in
(10 mm)
®