Parameter Settings (Default) - nVent RAYCHEM HWAT-ECO-GF Manuel D'installation, D'utilisation Et D'entretien

Masquer les pouces Voir aussi pour HWAT-ECO-GF:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SELECT ALARM
14 : 17
SELECT SAVING TIME
Water Temp. & Programming
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
14 : 17
Maintain /
Economy
temperature
14 : 17
Building type
program
Timer
schedule

5. PARAMETER SETTINGS (DEFAULT)

Language
Country
Date
Time
Building program
Heating cable type
Pipe diameter
Insulation thickness
Maintain temperature
Economy temperature
Low temperature limit
High temperature limit
Alarm sound
Key lock
WATER TEMP. & PROGRAM
The maintain temperature is the water temperature that
you set for normal use. The minimum temperature is 98°F
(37°C) or the economy temperature, whichever is
higher. The maximum temperature depends on cable type,
pipe thickness, insulation thickness and ambient
temperature. The economy temperature is the water
temperature for periods in which the amount of hot water
used is low (at night) or high (peak period). Select the
temperature using the + / - keys. The minimum temperature
is 98°F (37°C) for use in environments such as schools, and
105°F (41°C) in the Apartments program. The maximum
temperature is the selected maintain temperature.
The HWAT-ECO-GF has 7 default timer programs. Select
by tapping on the program of choice (box will turn red).
See figure xx for the schedule of each program.
The building program reflects the tapping profiles.
Graphically program the Timer in 1 hour time blocks.
You can set a block to OFF, Economy temp,
Maintain temp, or HEAT-UP*
OFF
ECONOMY
MAINTAIN
(*HEAT-UP=158°F [70°C] or 100% power (when the power
can't reach 158°F [70°C] ) only when using the HWAT-R2
or HWAT-P1 cable. This is the legionella control mode
and it is not pre-programmed. Activate this preferably
during night hours to minimize risk of scalding. Use the
modes button to overwrite the timer schedule. Select a
temperature mode to assign to the time bock of choice.
English
Not pre-defined; to be selected
--/--/2022 or last saved date
00:00; or last saved time
Not pre-defined; to be selected
Not pre-defined/ to be selected
1" (DN 25)
1"
HWAT-R2 131°F (55°C)
HWAT-P1 122°F (50°C)
HWAT-R2 122°F (50°C)
HWAT-P1 113°F (45°C)
95°F (35°C)
HWAT-R2 185°F (85°C)
HWAT-P1 149°F (65°C)
ON
OFF
OFF
ON
14 : 17
131°F/122°F
HOTEL
HEAT-UP
nVent.com/RAYCHEM
EN
FR
|
23

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Hwat-r2Hwat-p1

Table des Matières