Accessories; Connecting Flanges; Remote Control; Building Management Technology - Dimplex SI 50TUR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SI 50 - 70 TUR
4

Accessories

4.1 Connecting Flanges

The device can optionally be switched to flange connection
using the flat-sealing connection flange.

4.2 Remote control

A remote control adds convenience and is available as a special
accessory. Operation and menu navigation are identical to
those of the heat pump manager. Connection takes place via an
interface (special accessories) with RJ 12 Western plug.
NOTE
In the case of heating controllers with a removable operating
element, this can also be used directly as a remote control.
4.3 Building management
technology
The heat pump manager can be connected to a building man-
agement system network via supplementation of the relevant
interface plug-in card. The supplementary installation instruc-
tions of the interface card must be consulted regarding the
exact connection and parameterisation of the interface.
The following network connections can be made on the heat
pump manager:
Modbus
EIB, KNX
Ethernet
CAUTION!
If the heat pump or circulating pump is controlled externally,
an flow rate switch is required to prevent the compressor
from being switched on when there is no volume flow.
www.glendimplex.de
5

Transport

A lift truck is suited for transporting the unit on a level surface.
The device can be lifted from the rear or front on even ground
using a lift truck or fork-lift truck for transportation.
CAUTION!
The heat pump must not be tilted more than 45° (in any
direction).
After transportation, the transport fastening in the device is to
be removed from both sides of the base.
X
CAUTION!
Before commissioning, the transport fastening must be
removed.
All panelling can be removed to allow accessing the inside of the
device.
To remove the panelling, open the individual covers by un-
screwing the respective turn-lock fasteners and then gently tilt-
ing the covers away from the device. Then lift them up out of
the mountings. The rear panelling is fixed with screws that have
to be loosened to remove the panels.
452237.66.55 · FD 0007
English
X
EN-5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Si 70tur

Table des Matières