Type 2 (For Capacity Control) - Mitsubishi Electric CITY MULTI PAC-AH001-1 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.3.2 Type 2 (for capacity control)

Cooling
─ Set point temperature = -5.625 X Ain + 100.4 [°F] [Ain = Input Voltage]
─ Figure 8.3.2.1 below shows the relationship between the input voltage from the 3rd party controller and
the set point temperature for Type 2 Control in cooling mode.
Setting Temperature
Input Voltage
Fig 8.3.2.1
Heating
─ Set point temperature = 5.625 X Ain + 40.775 [°F] [Ain = Input Voltage]
─ Figure 8.3.2.2 below shows the relationship between the input voltage from the 3rd party controller and
the set point temperature for Type 2 Control in heating mode.
Setting Temperature
Input Voltage
Fig 8.3.2.2
PAC-AH001-1
45