8.3.2 Type 2 (for capacity control)
Cooling
─ Set point temperature = -5.625 X Ain + 100.4 [°F] [Ain = Input Voltage]
─ Figure 8.3.2.1 below shows the relationship between the input voltage from the 3rd party controller and
the set point temperature for Type 2 Control in cooling mode.
Setting Temperature
Input Voltage
Fig 8.3.2.1
Heating
─ Set point temperature = 5.625 X Ain + 40.775 [°F] [Ain = Input Voltage]
─ Figure 8.3.2.2 below shows the relationship between the input voltage from the 3rd party controller and
the set point temperature for Type 2 Control in heating mode.
Setting Temperature
Input Voltage
Fig 8.3.2.2