FX2N Series Programmable Controllers
ENG
*1 Internal 24V DC
*2 FX
-10PG inputs and outputs need to be
2N
supplied from external power supply. For
power consampution of the input and output,
please see FX
*3 FX
series PLC cannot connect together
2N
with an FX
2N
A n F X
- 3 2 A S I - M m o d u l e c a n n o t b e
2 N
attached to an FX
an FX
-16CCL-M module. Only one FX
2N
32ASI- M module can be connected to the
PLC.
*4 Maximum number of I/O points per system
Connection is allowed as far as the following
condition is satisfied:
(Actual nu mb er of I/O points of PLC) +
(Num be r of p oints oc cu pied by sp e cial
ex te n s io n blo ck s ) + (N u mb e r o f po i nt s
occupied by FX
Number of remote I/O modules) ≤ 256
Moreover, if connecting two or more FX
1 6C CL -M, the firs t ma s te r mo d ule c a n
connect to the "remote I/O modules" and
"remote device modules" but subsequent
modules can only connect to "remote device
modules".
FRE
*1 24 V CC interne
*2 Les entrées et sorties du FX2N-10PG doivent
être alimentés avec une tension externe. Des
indications sur la consommation des entrées
et sorties sont mentionnées dans le manuel
du FX2N-10PG.
*3 Dans un API de la série FX2N, aucun FX2N-
32ASI-M ne peut être exploité ensemble avec
un FX2N-16CCL-M. Un FX2N-32ASI-M ne
peut pas être raccordé à un API de la série
FX2N, dans lequel un FX2N-16CCL-M est
utilisé. Seul un FX2N-32ASI-M peut être
raccordé.
*4 Le nombre maximal d'adresses E/S par
système peut être utilisé tant que la condition
suivante est satisfaite : (Nombre E/S de
l'a ppa re il de bas e) + (No mbre E/S de s
a p p a r e i l s d ' ex t e n s i o n e t d e s m o d u l e s
spéciaux) + (Nombre d'adresses qui sont
affectées par FX2N-16CCL-M : 8) + (32 x
nombre de modules E/S décentralisés) £ 256
Lors d'utilisation de plusieurs FX2N-16CCL-
M, le 1er module maître peut être relié avec
le s " mo du le s E /S d éc e ntra lis és " e t le s
"appareils décentralisés" mais les autres
F X 2 N - 1 6 C C L - M s e u l e m e n t a v e c l e s
"appareils décentralisés".
-10PG User's Manual.
2N
-32ASI-M and FX
-16CCL-M.
2N
series PLC that is using
2N
-16CCL-M: 8) + (32 x
2 N
*5 The value depends on the switch setting (32,
64, 96 or 128 points). However, the number of
connected master blocks can be arbitrary as
far as the total number of I/O points of a basic
unit, master blocks, extension units/ blocks
and special extension units/blocks (occupying
eight input or output points) is equal to 256
points or less.
*6 When using a twisted-pair cable, current
consumption is 20mA. When using a optical
-
2N
glassfiber cable, current consumption is
60mA.
*7 The I/O control points of both the FX
32ASI-M and PLC CPU must not exceed 128
points. Therefore, there is a limitation in the
number of units (number of slaves) which can
be controlled according to the I/O points
recognized by the PLC's CPU (occupation).
Occupation I/O points: Each AS- i slave
station occupies 4 CPU I/ O points.
-
*8 FX
2N
2N
Typical 30.5V) from the AS-interface power
supply.
*5 La valeur dépend du réglage du commutateur
(32, 64, 96 ou 128 adr.). Le nombre de
modules maîtres pouvant être installés est
toutefois limité par la plage d'adresse de l'UC.
La somme des adresses E/S de l'appareil de
base, des appareils d'extension, des modules
maîtres et des modules spéciaux (affectant 8
entrées et sorties) ne doit pas être supérieure
à 256.
*6 Lors de l'utilisation d'une ligne torsadée à
deux fils, la consommation est de 20 mA.
Po u r u n e l i g n e à f i b r e s o p t i q u e s , l a
consommation est de 60 mA.
*7 La somme des adresses E/S du FX2N-
32ASI-M et de l'UC de l'API ne doit pas
dépasser 128. Ainsi, il y a une limitation du
nombre d'unités (nombre d'esclaves) qui
peuvent être raccordées et reconnues par
l'UC. Ad re ss e s E /S a ffe c té e s : c h aq u e
module esclave AS-i affecte 4 entrées et 4
sorties.
*8 Le FX2N-32ASI-M est alimenté en tension via
un module d'alimentation AS-I externe (type
30,5 V) et consomme 70 mA.
Introduction 1
-32ASI-M must be supplied 70mA (at
1-6
-
2N