Holding register
Nom
(Protocol)
40014
Bus command timer
(13)
40015
Drives on/off
(14)
40025
Control mode
(24)
40026
Current value
(25)
40041
Pump 1 mode
(40)
40042
Pump 2 mode
(41)
40043
Pump 3 mode
(42)
40062
Switch box state
(61)
Notice de montage et de mise en service • Wilo-Control EC-L • Ed.04/2022-09
Type de don-
Échelle et unité
nées
ENUM
BOOL
ENUM
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
ENUM
ENUM
ENUM
BITMAP
Éléments
Accès*
0. -
RW
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW
0. p-c
R
1. dp-c
2. dp-v
3. dT-c
4. dT-v
5. n(TV)
6. n(TR)
7. n(TP)
8. n(TA)
9. n-c
10. fill
11. empty/drain
12. FTS
13. cleans/day
14. cleans/
month
R
0. Off
RW
1. Hand
2. Auto
0. Off
RW
1. Hand
2. Auto
0. Off
RW
1. Hand
2. Auto
0 : SBM
R
1: SSM
fr
Ajouté
31.000
31.000
31.000
31.000
31.000
31.000
31.000
31.000
61