1 MΩ. Alternatively, the differential-current
method in combination with measuring the
PE conductor current can be used. A value of
3.5 mA must not be exceeded in either case.
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urements must be performed in adapter state C.
The differential-current measurement must
be performed at the connection point of the
charging system's supply cable in the building's
electrical cabinet.
Depending on the measuring instrument
i
used, it might not be possible to perform
the following measurement on the
adapter. In this case, perform the test at
the connection terminals.
Testing the switch-off condition in the event of a
short circuit (Z
)
L-N
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urements must be performed in adapter state C.
Perform the measurements at the test adapter's
measuring sockets. The values in accordance with
the selected circuit breaker must be observed.
Testing the switch-off condition in the event of
the RCD tripping
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urement must be performed in adapter state C.
Perform the measurement at the measuring
sockets of the test adapter using a suitable
measuring instrument. The values in accordance
with the selected RCD and the network must be
observed.
Testing the integrated DC residual current
detection
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urements must be performed in adapter state C.
Perform the measurements at the test adapter's
measuring sockets using a suitable measuring
instrument. The charging system must discon-
nect the charging coupler from the mains when
the residual current exceeds 6 mA DC. The fault
display on the charging system must respond.
26
1.6
Information about signs, symbols
and labelling
Hazard warning:
Information about a possibly hazardous situation
that could be fatal or result in severe injuries if the
safety measures are not observed. All work is to be
performed by skilled personnel only.
Note:
More information is available in the operating
instructions.
Note:
i
supplementary information.
1.7

Protective devices

The following components (Fig. XVI) are protective
devices:
1 housing, 2 charging cable, 3 protective cover,
4 charging coupler
Checking the protective devices
» 1. Visually inspect the protective devices for
damage before every charging process.
» 2. Have a qualified electrician perform the
electrical function tests at regular intervals in
compliance with the national regulations.
1.8
Type plate, front illumination and
blocking device
1.8.1

Type plate

You can find the type plate of the Wallbox as shown
in Fig. XVI no 2.
1.8.2

Front illumination

The front illumination (Fig. XVI no. 1) indicates
the operating state of the charging system. Refer
to the operating instructions for details of the
operating states.
The charging process starts automatically as
soon as the charging coupler is inserted and the
vehicle requests the charging process.

Publicité

Table des Matières
loading

Table des Matières