9.
Taking into operation
Prior taking into operation it is necessary to check the correct function, the
correct working order and the installation of the emergency luminaire in
compliance with these operating instructions and the operating instruc-
tions
ExLin NE+ (300 8000 2309) ,
as well with any other applicable stipulations!
10. Operation and fault indication
See diagram on "Technical data",
"Operation and fault indication".
Maintenance
11.
Isolate the equipment from the power supply before opening it!
Only use original Cooper Crouse-Hinds / EATON spare parts.
When carrying out maintenance work, servicing and tests on
explosion-protected equipment, the applicable regulations,
e.g., IEC/EN 60079-17 shall be observed!
When servicing and carrying out repairs, the safety instructions
and data contained in the operating instruction
ExLin NE+ (300 8000 2309)are also to be observed.
The required maintenance intervals are set according to their application
and should therefore be determined depending on the conditions of use.
-
Enclosure and cover for cracks and damage.
-
Seals for damage.
-
Contacts and Ex-d pin contacts have to be clean and free of corrosion
and have not to be bent.
Because of the risk of an electrostatic charge, the light fitting shall only be
cleaned with a damp cloth or sponge!
Only use customary household washing-up liquid diluted in water as
specified! The water temperature may be max. 50 ºC. After that, rinse with
clear water.
If during servicing repairs prove to be necessary, section 12 of these
operating instructions will have to be observed.
Battery pack NE+ for ExLin NE+
11.1 Change battery pack
buildet in and operated into the luminaire:
ExLin 3L-1 NE+ and
ExLin 5L-1 NE+
The battery pack may be installed in the ExLin NE+ luminaire in zones 1
and 21 explosive atmospheres.
X
ATEX - IEC
that no dirt or dust gets into the luminaire when the battery pack is
installed.
Sealing surfaces must be free of dirt and dust.
Battery charging starts when the power is switched on.
12. Repairs / Overhaul / Modification
Repairs that affect the explosion protection, may only be carried
out by COOPER CROUSE-HINDS or a qualified electrician (Competent
person) in compliance with the applicable national rules
(IEC/EN 60079-19).
For replacement and repair only original parts from COOPER CROUSE
HINDS-/ EATON may be used.
Modifications to the device or changes of its design are not permitted.
They shall be used for their intended purpose and in perfect and clean
condition.
13. Disposal/Recycling
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
In case of disposal you can obtain additional information from your Cooper
Crouse-Hinds / EATON branch.
In order to facilitate the recycling of individual components, plastic parts
are provided with the identification mark of the plastic material used.
Subject to modifications or supplement of the product range.
The battery pack for the lightifitting ExLin NE+ have to be only
In areas with process-related dirt or dust, have to be to ensure
GB
11