Wiring the device modules
Communication modules
DIP switch
Pos.
Description
A
Addressing of the station
For addressing purposes, every station must be given an unambiguous address.
Valid address range: 1  126
The address can be set freely via the front−panel switch.
)
Note!
ƒ
ƒ
Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.
Address settings through the DIP switch (device front)
The sum of the values (identical with package labelling) results in the station address to be
set:
Example:
Switch
Package labelling
Switch state
Address (= 23)
Displays
LED
Pos.
Colour
MS
Green
ME
Red
BS
Green
BE
Red
DE
Red
70
For S1 − S7 = OFF (Lenze setting):
When switching on the module, the configuration set under code C00899
becomes active.
For one of the switches S1 − S7 = ON:
When switching on the module, the address resulting from the switch
setting becomes active.
S7
«64»
0
0
Condition
Description
On
The communication module is supplied with voltage and connected to
the standard device.
Blinking
The communication module is supplied with voltage, but has no
connection to the standard device. (The standard device is switched off,
initialising, or not present.)
On
An error in the communication module has occurred.
Blinking
Communication via the communication module has been established.
PROFIBUS communication is active.
On
Bus monitoring has been triggered.
On
The communication module is not accepted by the standard device. (See
notes in the documentation for the standard device.)
l
S6
S5
S4
«32»
«16»
«8»
0
1
0
0
16
0
S3
S2
S1
«4»
«2»
«1»
1
1
1
4
2
1
EDK94ARN24 DE/EN/FR/ES/IT 3.0