Determine the intended location and clean the adhesive
areas! Ensure a firm and correct fit of the individual
components.
12) Finally route the line of the thermo-sensor (10) as far as
the furnace transmitter (9).
FUNCTIONAL TEST
The temperature at the thermo-sensor (10) of the furnace
transmitter (9) is crucial for the function testing of the
exhaust air control.
Thermo-sensor (10) of the furnace transmitter
is < 38°C
1. Switch ON exhaust unit and window is closed
>
Exhaust unit must start up.
2. Open window
> Exhaust unit must remain on.
3. Close window
> Exhaust unit must remain on.
Thermo-sensor (10) of the furnace transmitter
is > 38°C
1. Switch ON exhaust and window is closed
>
Exhaust unit must not start up.
2. Open window
> Exhaust unit must start up.
3. Close window
> Exhaust unit must switch off.
MEANING OF THE LED DISPLAYS
RECEIVER/CONTROL CENTRE
LED Network (3)
Yellow continuously lit
> Basic position
Yellow flashing at the start > No transmitter taught in
Yellow flashing Teach-in mode > Transmitters can
LED Window (4)
Dark
Green continuously lit
Red continuously lit
RED and GREEN continuously lit > Window transmitter no
LED Furnace (5)
Dark
Green continuously lit
Red continuously lit
RED and GREEN continuously lit > Furnace transmitter no
WINDOW TRANSMITTER
Dark
Green flashing
Red flashing
RED and GREEN flashing 0.5 s > Window transmitter
FURNACE TRANSMITTER
Dark
Green flashing
Red flashing
Battery control LED
flashing 0.5 s
19
ENGLISH | AS-5030
be taught in
> No transmitter taught in
> Window is open
> Window is closed
longer has radio reception
(Battery discharged,
defective or no radio
reception)
> No transmitter taught in
> Furnace is cold
> Furnace is hot
longer has radio reception
(Battery discharged,
defective or no radio
reception)
> Rest state / Sleep mode
> Window is being opened
> Window is being closed
battery is discharged
> Rest state / Sleep mode
> FURNACE becoming cold
> FURNACE becoming hot
> FURNACE transmitter
battery discharged