Rollixo Smart io
WARNING
The earth wire must always be longer than the live and neutral to ensure that it is the last to be disconnec-
ted if the connector is pulled out.
The cable clamp supplied must be used.
For all low-voltage cables, ensure that they can withstand traction of 100 N. Check that the conductors do
not move when this traction is applied.
3.5
Safety edge wiring
DANGER
Wiring a safety edge is compulsory.
The operation must be carried out with the power off.
3.5.1
Connect the safety edge
Optical wired safety edge
> > > Illustration 8
Translation of the colours present on the safety edge wiring diagram:
EN
EN
Brown
Brown
Green
Green
White
White
Wired resistive safety edge 1.2 kΩ or 8.2 kΩ.
> > > Illustration 9
3.5.2
Adjust setting P2 according to the type of safety edge connected
1] Press the "SET" button for 0.5 s to enter parameter setting mode.
ð Indicator light P0 flashes once.
2] Press the "SET" button twice to move on to parameter P2.
ð Indicator light P2 flashes once to indicate the value selected.
3] Press the "+" or "-" button to change the value of the parameter.
ð The indicator light flashes x times to indicate the value selected.
• P2 = 1 x: Optical wired safety edge
• P2 = 2 x: Resistive wired safety edge 1.2 kΩ
• P2 = 3 x: Resistive wired safety edge 8.2 kΩ
4] Press the "SET" button for 2 s to confirm a value and exit parameter setting mode.
ð The parameter setting indicator lights go out.
©