INSTALLATION continued
Less than 10 feet (3 meters)
2' (60cm)
Min.
Termination Less than 10 feet (3 meters) from ridge
Testing & Lighting Instructions
1. Turn on main gas valve. Remove the lower front cover
and the service panel above the control panel. Drop the
control panel and leak test all fi ttings and connections
upstream from the service valve located on the redundant
combination gas valve. Should any gas leaks be detected,
turn OFF main gas valve, correct the problem and retest.
2. Open shutoff valve located on the redundant combination
gas valve. Activate control panel and set to desired
temperature. The pilot burner is ignited by direct spark,
main burners are then ignited by the pilot. Check all
fi ttings again and correct any leaks and recheck.
Replace all service panels and covers before operation.
NOTE: All electronic ignition systems are supplied with a
redundant gas valve. Therefore, the unit is not supplied with
an external pressure regulator.
10
3' (90cm) Min.
Termination More than 10 feet (3 meters) from ridge
NOTE: During installation there will be air in the gas line. This
air will have to bleed off before ignition can be established.
The electronic ignition system has a ninety second lock-out
as a safety device on all units. Therefore, several attempts
may be required before pilot ignition is established, wait fi ve
minutes after each attempt.
FOR YOUR SAFETY: KEEP YOUR APPLIANCE AREA FREE FROM
Do not waste energy by leaving controls at high temperature
settings during idle periods. Lower settings will keep
oven warm and ready for next use period. Master 400
Series controls have an auto setback feature that is user
programmable to help with these applications.
More than 10' (3 meters)
COMBUSTIBLES.
TO CONSERVE ENERGY:
Part Number 1955200 rev 7 4/15
3' (90cm) Min.