Error
|Power outage|
|Relay error 1
2|
or
|Communication
error|
All error messages listed here are forwarded to the potential-free contact if it has been connected and activated properly.
016-003_03
Cause
Power supply has failed
Control unit fuse faulty
Mains supply cable is interrupted
Power contactor does not switch off
Connection cable between the main control
unit and the redundant closure control unit
is defective
Connection to the TeleControl modem is
interrupted
Connection to LIN master is interrupted
Remedial measures
None, general power outage
Determine the reason for the tripped fuse
and replace the fuse if necessary
Check mains supply cable
Disconnect the control unit from the mains,
replace the contactor
Check / repair cable connection
No credit, no network signal, add-on unit
has failed
Restore the connection of the LIN, RS232,
RS485 connection cable
53 / 164