TABLE OF FUNCTIONS AND INSTALLER PARAMETERS
Function
Parameter Description
System configuration
54
Type of user interface
Control panel
software release
Control panel
software version
Output test
Reset pump run-time
External heat source/
defrosting
Humidity limit
Auxiliary source
required for ACS or
humidity control
Frost Delta set point
Compressor run-time
reset
Flow switch status
Heating climate curve
number
Heating water set
point
Heating temperature
reduction in eco mode
Cooling water set
point
Cooling temperature
reduction in eco mode
Cooling climate curve
number
Min outdoor air
temperature in heating
mode
Max outdoor air
temperature in heating
mode
All manuals and user guides at all-guides.com
Code used to set the type of system:
1. Heat pump with fixed water temperature (clean contacts)
2. Heat pump with set-up of the climate curve (clean contacts)
3. Heat pump with control panel control
100
4. Monoblock Comfort with Control Panel as Thermostat
5. N.A.
6. Monoblock RS485
7. N.A.
Code used to indicate if and how the User Panel control interface is used:
0. Control panel not used (Input Relay active)
101
1. Control panel installed
2. Control panel used as programmer
102
The code indicates the Control panel software release
103
The code indicates the Control panel software version
Code used to force the Output ON to carry out the test (max 10 minutes)
0. No test
1. Water pump
2. Alarm/Ambient temperature reached
3. External heat source /Defrost
104
4. Auxiliary heat source required for ACS/Dehumidification
5. Electric trace heater / Additional water pump
6. 3-way valve
7. Not used
8. Not used
105
This code is use to reset the water pump working hours to zero
Code is used to select the output connected to PIN 4 on the terminal board
106
1. Auxiliary heat source required
2. Defrost output signal
Code used to set the humidity threshold limit to enable the output for the external
107
de-humidifier system
Code used to select the output connected to PIN 11 on the terminal board
1. Auxiliary source required for ACS when External Air Temperature <
108
temperature set with code 148
2. Humidity control
Code used to set the frost set point delta used by the antifreeze system as per
109
algorithm
110
Code used to reset the compressor working hours to zero
The code displays the status of the flow switch:
111
0. Water not flowing
1. Water flowing
Code used to select the number of the heating climate curve.
112
0. No pre-set climate curve (the installer has to draw up the Climate Curve)
1-12. For more information on the curves, read the specific section
113
Code used to set the fixed set point of the heating water
Code used to set the temperature reduction value for the fixed set point of the heating
114
water when the unit is in ECO mode.
115
Code used to set the fixed set point of the cooling water.
Code used to set the temperature reduction value for the fixed set point of the cooling
116
water when the unit is in ECO mode.
Code used to select the number of the cooling climate curve.
117
0. No pre-set climate curve (the installer has to draw up the Climate Curve)
1-2. For further information on the climate curves consult the control panel manuals.
Code used to select the minimum outdoor temperature of the heating climate curve,
118
which depends on the country where the system is installed.
119
Code used to select the maximum outdoor temperature of the heating climate curve. 10°C
HYDRONIC UNIT LE B
Value range
Min
no
20
0°C
No
20°C
1°C
4°C
1°C
-20°C +10°C
Default
Set
value
value
Max
1
7
1. A2W
0
2
0. Not used
-
-
-
Lock
-
-
-
Lock
0
8
0. No test
yes
no
1
2
1
100
50%
1
2
2
6°C
1°C
yes
No
-
-
-
Lock
0
12
0
60°C
45°C
20°C
5°C
25°C
7°C
10°C
5°C
0
2
0
-7°C
30°C
30°C