Télécharger Imprimer la page

Tripp-Lite SmartOnline SUINT1000XLCD Manuel D'utilisation page 18

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 49
6. Turn-on, Cold Start & Turn-off Procedures
Note: Refer to 3. Operation Panel for details on the operation panel and the display meaning.
6.1 Turn-on Procedures
After the UPS is connected to the AC utility, the AC utility supplies power to the UPS. The UPS is
initially set In Standby Mode. To turn on the UPS, press and hold the
Release it after one beep.
6.2 Cold Start Procedures
Even when there is no utility power, the UPS can be turned on. Press and hold the
3 seconds. Release it after one beep and the UPS will start up and run in Battery Mode.
6.3 Turn-off Procedures
1. To turn off the UPS in On-line Mode, press and hold the
after hearing one beep. The inverter will turn off and the UPS will transfer to Standby Mode.
The UPS will keep charging the batteries when the UPS is in Standby Mode even though the
button has been pressed. To fully turn off the UPS, unplug the input power cord.
2. To turn off the UPS in Battery Mode, press and hold the
after hearing one beep. The UPS will turn off its output.
7. Alarm
Battery Mode: The audible alarm beeps once every 2 seconds.
Low Battery: The audible alarm beeps once every 0.5 second.
Bad Battery/Battery Replacement*: The audible alarm beeps once every 2 seconds.
Overload:
1. Overloaded 105-125%: The audible alarm beeps once every 2 seconds.
2. Overloaded 125-150%: The audible alarm beeps once every 0.5 second.
Fault: The audible alarm beeps continuously for 5 seconds if the UPS detects an internal fault.
* After reconnecting or replacing the batteries, it may take a short time for the UPS to switch off the alarm
automatically. If, after a period of time, the audible alarm still exists, the user should manually initiate a battery
test (press and hold the
18-09-252-93358B.indb 18
button for 3 seconds and release it after hearing one beep) to clear the alarm.
18
button for 3 seconds.
button for
button for 3 seconds. Release it
button for 3 seconds. Release it
1/9/2019 2:19:30 PM

Publicité

loading

Ce manuel est également adapté pour:

Smartonline suint2000xlcdSmartonline suint3000xlcd