5.1 Recommended installation position

► Install the unit so that the measuring pipe is always completely filled.
► Install in front of or in a rising pipe.
F = volumetric flow direction

5.2 Non-recommended installation position

• Directly in front of a falling pipe
• In a falling pipe
• Directly in front of the spout of a pipe
• On the suction side of a pump
• At the highest point of the pipe system

5.3 Ground

If installed in an ungrounded pipe system (e.g. plastic pipes), the unit must
be grounded (functional earth).
Ground brackets for the M12 connector are available as accessories
→ www.krohne.com.

5.4 Installation in pipes

The units with a G thread can be installed in the pipes using adapters.
Information about the available mounting accessories at www.krohne.com.