The system is prepared to carry out speed and operation tests manually through this menu. When you access this
menu, regardless of the status of the system, the unit from which you are accessing stops its functions and therefore
stops the pump.
When you access this menu this screen appears:
4 . M A N U A L
0 . 0 H z
4 . 0 B a r
E X I T
F1
4 . M A N U A L
4 2 . 0 H z
4 . 6 B a r
O f f
F1
ATTENTION:
Improper use of manual mode can cause overpressures in the installation.
Par.
Description
5.01 LANGUAGE
5.02 UNITS OF PRESSURE
MAXIMUM NUMBER OF PUMPS
5.03
ON
TRANSDUCER FULL-SCALE
5.04
VALUE
5.05 2 WORKING PRESSURE
5.06 PRINCIPAL STOP DELAY
4. MANUAL
Where you can see the frequency, an operation timer and the pressure
at that precise moment read by the transducer.
( 0 s )
Press F1 to exit this menu.
O N
When you press ON (with the F2 key) you will start the motor and you
can increases or reduce the frequency using the keys and . At
F2
the same time you can see how the countdown begins for 60 seconds
of operation. If you do not press any keys, after 60 seconds the motor
( 0 s g )
will stop automatically. If you press any keys during the test the
counter return to 60 seconds.
Press F1 to exit, stop the motor and return to the wait screen of this
menu.
5. ADVANCED PARAM.
Programming
Units
Default
Min.
Spanish
English
Spanish
French
Italian
Portuguese
Bar
Bar
Bar - Psi
8
1
Bar
Wizard
5
Bar
**
0.5
Sec
10
0
37
Max.
You can select between different languages for the
menu and the warnings.
Units of working pressure and display.
Maximum number of pumps that can function in the
8
system simultaneously.
25
Value of the transducer at 20 mA.
Second working pressure for installations that require it.
FS
** As a default value it will show 4 bar.
Time from the moment the main pump is working at a
100
speed below the stop frequency (parameter 1.4) until it
stops fully.
ENGLISH
Notes