11. SETUP MENU

Par.
Description
1.1
WORKING PRESSURE
1.2
MOTOR CURRENT
1.3
ROTATION DIRECTION
1.4
STOP FREQUENCY
1.5
START-UP DIFFERENTIAL
Wizard: This parameter is the one entered or calculated in the start-up wizard.
FS: Full-scale value of the transducer (entered in the start-up wizard).
Par.
Description
2.01 MODULE TEMPERATURE
2.02 ANALOGUE SIGNAL
2.03 VOLTAGE HOURS
2.04 HOURS WORKED
2.05 START-UP NUMBER
2.06 DIGITAL INPUT 1
2.07 DIGITAL INPUT 2
2.08 RELAY 1 OUTPUT
2.09 RELAY 2 OUTPUT
2.10 SOFTWARE VERSION
2.11 CONS. POWER OF PUMP
2.12 CONS. POWER OF GROUP
3 . 0 1
A L A R M
V O L T A G E
1 0 / 0 2 / 1 6
E X I T
F1
1. PARAMETERS
Programming
Units
Default
Min.
Bar
Wizard
0.5
Amp
Wizard
0
0
Hz
Wizard
0
Bar
0.5
0.3
2. DISPLAY
Units
ºC
This indicates the temperature the electronic module of the unit is at.
This indicates the value in mA of the pressure transducer. This data will be 4 mA for 0 Bar
mA
and 20 mA for the upper limit of the transducer connected.
Hours This indicates the total number of hours the unit has been connected to an electricity grid.
Hours This indicates the total number of hours worked (providing an output voltage) of the frequency converter.
This indicates the total number of start-ups from zero that the unit has made.
This indicates whether digital input 1 is ON or OFF.
This indicates whether digital input 2 is ON or OFF.
This indicates whether the relay 1 output is ON or OFF.
This indicates whether the relay 2 output is ON or OFF.
Version of the unit software.
W
Instantaneous power consumed in output terminals toward pump.
W
Power consumed instantaneously by all of the pumps.
3. LOG
F 0 4
-
1 2 : 1 9
Max.
FS
Pressure you wish to maintain in the system.
Current of the motor in amperes. Taking into account
11
whether your motor is wired as three phase 230V or
three phase 400V.
You can change the rotation direction of the motor by
1
modifying this parameter from 0 to 1 or vice versa.
The system will stop when the frequency converter has
99.9
been working for a certain time (see parameter 5.06)
below this frequency.
This is the differential that enables you to reduce the
3
pressure to start the pump using the value entered in
parameter 1.1.
Notes
When you access the log menu you will find a list in chronological order
of alarms that have been triggered in your unit, indicating the date
and the time they occurred
Use the arrows  and  to move forward or back to view the
different alarms that have been triggered.
Press F1 to exit this menu.
36
ENGLISH
Notes