7.
MAINTENANCE
7.1
Replacement of sensing probe
If the sensing probe gets damaged (e.g. mechanical destruction of the sensor probe) it is
possible to replace the probe without re-adjustment.
Procedure of replacement:
1) Switch off supply voltage
2) Remove damaged sensor probe
3) Plug in the replacement probe
Attention: Do not mix up the position of the probes!
(see chapter 3.1 "Mounting of the probe")
7.2
Self-help in case of errors
•
Error
possible cause
⇒
Measures / Help
•
Display shows incorrect values
Error during re-adjustment of the transmitter
⇒
Reset to factory calibration and repeat the calibration routine
Filter soiled
⇒
Replace filter
Sensor defective
⇒
Replace sensor
•
Long response time
Filter soiled
⇒
Replace filter
Incorrect filter type
⇒
Filter type should match the application
•
Transmitter failure
no supply voltage
⇒
Check wiring and supply voltage
•
High humidity values
Dew (condensation) in sensor probe head
⇒
Dry probe head and check the mounting of the sensor probe
Incorrect filter type
⇒
Filter type should match the application
8.
REPLACEMENT PARTS / ACCESSORIES
Description
- Display and housing cover in metal
- Display and housing cover in polycarbonate
- Duct mounting kit
- Reference probes
- Probe cable 2m
/ 5m
(6.6ft)
- Bracket for rail installation
- External supply unit
/ 10m
(16.4ft)
(32.8ft)
(for polycarbonate housing only)
18
Order Code
D07M
D07P
HA010209
HA010403
HA0108xx
HA010203
V02