MAINTENANCE

7.1

Replacement of sensing probe

If the sensing probe gets damaged (e.g. mechanical destruction of the sensor probe) it is
possible to replace the probe without re-adjustment.
Procedure of replacement:
1) Switch off supply voltage
2) Remove damaged sensor probe
3) Plug in the replacement probe
Attention: Do not mix up the position of the probes!
(see chapter 3.1 "Mounting of the probe")
7.2

Self-help in case of errors

Error
possible cause
Measures / Help
Display shows incorrect values
Error during re-adjustment of the transmitter
Reset to factory calibration and repeat the calibration routine
Filter soiled
Replace filter
Sensor defective
Replace sensor
Long response time
Filter soiled
Replace filter
Incorrect filter type
Filter type should match the application
Transmitter failure
no supply voltage
Check wiring and supply voltage
High humidity values
Dew (condensation) in sensor probe head
Dry probe head and check the mounting of the sensor probe
Incorrect filter type
Filter type should match the application
8.

REPLACEMENT PARTS / ACCESSORIES

Description
- Display and housing cover in metal
- Display and housing cover in polycarbonate
- Duct mounting kit
- Reference probes
- Probe cable 2m
/ 5m
(6.6ft)
- Bracket for rail installation
- External supply unit
/ 10m
(16.4ft)
(32.8ft)
(for polycarbonate housing only)
18
Order Code
D07M
D07P
HA010209
HA010403
HA0108xx
HA010203
V02

Publicité

Table des Matières
loading

Table des Matières