Télécharger Imprimer la page

Festo CPX-FVDA-P Description Sommaire page 39

Masquer les pouces Voir aussi pour CPX-FVDA-P:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
CPX-FVDA-P
Technical data
– Max. peak current per channel
– Max. residual current per module
– Voltage drop per channel under
continuous load
– Wire break detection (CH1, CH2)
– Cable length (CH1, CH2)
– Load capacitance to FE
– Load capacitance P-M
– Load inductance
– Fuse protection (short circuit)
– Switching logic at outputs
Functional characteristics
– Module code
– Sub-module code
Safety characteristics
– Safety function
– Disconnection scheme by channel
– Diagnostics of external channel fault
– Response time to internal faults
– Response time for external channel
errors
Festo CPX-FVDA-P-Z6 1303a English
CPX-FVDA-P
[A]
5, for t < 50 ms
[A]
5
[V]
Max. 0.6
configurable, I
[m]
Max. 200
[nF]
Max. 100
[µF]
Max. 2.2
[mH]
1000 at 150 mA, 100 at 600 mA; for
characteristic curve
product P.BE-CPX-FVDA-P
Integrated electronic fuse per channel
PM switching
193d (C1h)
1d (01h)
Safe switch off of the output channels
– in accordance with EN 61508 with SIL 3
– in accordance with EN ISO 13849 with
cat. 3, PL e
– in accordance with EN 62061 with
SIL CL 3
P and M switching
– Cyclic check for function
– Cyclic check for external supply
– Cyclic check for cross circuit
[ms]
< 100
[ms]
< 220
< approx. 50 mA
L
description of
39

Publicité

loading