Section 4
CLEANING/SANITIZING PROCEDURE RN1000/RN1400
Use Ice Machine Cleaner part number 000000084.
Use Ice Machine Sanitizer part number 94-0565-3.
Step 1 Remove all ice from the bin/dispenser.
Step 2 Remove front and top covers.
Step 3 Mix a solution of cleaner and water.
Amount of Luke Warm
Water
1 gallon (4 Liters)
Step 4 To start a cleaning cycle, depress the CLEAN
switch to drain the water from the evaporator. Wait for
the LOW WATER light to energize.
Step 5 Remove cover from the cleaning cup and add
cleaner/water solution until the HI WATER light
energizes, then replace cleaning cup cover. The
machine will clean and then flush three times in
approximately twelve minutes.
Step 6 While the ice machine is in the clean cycle,
prepare for the sanitizing cycle by mixing a solution of
sanitizer and water.
Amount of Luke Warm
Water
1 gallon (4 L) Water
Step 7 To start a sanitize cycle, depress the clean
switch to drain the water from the evaporator. Wait for
the LOW WATER light to energize.
Step 8 Remove cover from the cleaning cup and add
sanitizer/water solution until the HI WATER light
energizes, then replace cleaning cup cover. The
machine will sanitize and then flush three times in
approximately twelve minutes.
Part Number 000007282 4/10
Amount of Cleaner
Part Number 000000084
4 ounces (120 ml)
Amount of Sanitizer
Part Number 94-0565-3
1/2 ounce (15 ml)
Step 9 Press the OFF switch, then unscrew the ice
chute connector.
Step 10 Using disposable food service grade gloves
insert one dry sponge into the transport tube going to the
evaporator (NOT the tube going to the bin), then insert
one sponge soaked in the sanitizer water solution. With
the pusher tube supplied with the sponge kit, push
sponges all the way down the transport tube 16 inches
(41 cm) or the length of the pusher tube.
Step 11 Reconnect chute connector and press the ON
switch. Allow the ice machine to run for 10 minutes, then
press the OFF switch. Catch and remove all sponges
and ice from the bin/dispenser.
Step 12 Clean and sanitize the bin/dispenser:
•
Disconnect power to the dispenser to prevent injury.
•
Use the cleaner and sanitizer ratios from the charts
on this page.
•
Heavy accumulations of scale will require removal of
components for cleaning and sanitizing.
•
Rinse parts with clear water after cleaning - do not
rinse parts after sanitizing.
Step 13 Spray all interior bin/dispenser surfaces with
sanitizer (do not rinse sanitized areas).
Step 14 Place rocker switch in the ON position and
reinstall all removed panels.