INSTALLATION INFORMATION

WARNING: check that the power
supply is disconnected before carrying
out any procedures on the unit.
WARNING:before carrying out any
work, put the proper individual
protection equipment on.
WARNING: the device must be installed
in compliance with the national plant
engineering rules.
WA R N I N G : e l e c t r i c a l w i r i n g s ,
installation of the fan coils and
relevant accessories should be
performed by a technician who has the
necessary technical and professional
expertise to install, modify, extend and
maintain systems, and who is able to
check the systems for the purposes of
safety and correct operation.
WARNING: install a device, main
switch, or electric plug so you can
fully disconnect the device from the
power supply.
WARNING: Consult all documentation
before starting the installation.
The essential indications to install the
device correctly are given here.
The completion of all the operations
in accordance with the specific
requirements is however left to the
experience of the installation engineer.

ALARM CODES

This section is reserved for the After Sales
service only.
The card is located inside the unit and
requires dismantling.
DANGER! Only qualified service
personnel can access it.
There are 2 LEDs on the Inverter card
(Alarm / Power) that indicate the unit's
operating status.
The table below shows how to decode
the messages.
ALARM TYPE
High temperature
Overvoltage
Undervoltage
Overcurrent
Overload
Safety control
STOP
IFCXIUASLJ 1210 - 5383600_04
16
The water, condensate discharge
and electrical circuit ducts must be
provided for.
The fan coil must be installed in such a
position that the air can be distributed
throughout the room and so that there
are no obstacles (curtains or objects) to
the passage of the air from the suction
louvers.
The fan coil should be installed in such
a way as to facilitate routine (filter
cleaning) and special maintenance
operations, as well as access to the
air drain valve on the side of the unit
frame (connections side).
Do not install units in rooms where
there are inflammable gases or acid
or alkaline substances that could
irretrievably damage the aluminium-
copper heat exchanger or the internal
plastic parts.
Do not install the unit in workshops or
kitchens where the oil vapours mixed
with the treated air can be deposited
on the exchange coils, reducing their
performance, or on the parts inside the
unit, damaging the plastic parts.
If a three-way valve is installed, the
minimum water temperature sensor
can be installed in two locations:
- i n
i t s
h o u s i n g
MANDATORY if the thermostat is
FCXI20
FCXI30
FCXI40
FCXI50
LEDS
Alarm
Power
INDICATIONS
ALARM LED flashes
3sec ON 0.5sec OFF
The LED if permanently ON
after 1.5min
ALARM LED flashes
0.5sec ON 0.5sec OFF
Alarm LED permanently on
connected to a system with centralised
control or monitoring device (example:
VMF-E5);
- on the delivery pipe up stream of the
valve.
Check the thermostat manual before
choosing the location of the minimum
water temperature sensor, according
to the preferred control logic. The
thermostat may need the settings of the
dip-switches changed.
WA R N I N G : A f t e r c o m p l e t i n g t h e
installation check the operation of the
condensate discharge system, the seal
of the hydraulic fittings, insulation
of ducts and pipes. Then perform a
functional test.
In the event of malfunction consult the
Alarm Codes Table to interpret the
alarms indicated by the 2 LEDs (Alarm
/ Power) that indicate the status of the
unit.
The inverter card is located inside the
unit and requires dismantling.
i n
t h e
c o i l ,
FCXI80
IRREGULARITY
Motor off
Speed reduction
Motor off
DANGER! Only qualified service
personnel can access it.
Notes
Auto-Restart Alarm.
If the conditions persist after
1.5min, the alarm becomes
permanent, the Alarm LED stays
on, the system turns off.
Power limitation
Temperature limitation
For alarms reset:
Set 0V ON INPUT
(turn the power off and then on again)