Télécharger Imprimer la page

Parker PSE Serie Manuel D'utilisation page 20

Masquer les pouces Voir aussi pour PSE Serie:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
English
6 Maintenance
a) The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) Z When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the data plate located on the
unit.
c) Circuits containing 5t < xx < 50t of CO2 are checked to identify
leaks at least once a year.
Circuits containing 50t < xx < 500t di CO2 are checked to identify
leaks at least once every six months. ((EU) No. 517/2014 art. 4.3.a,
4.3.b).
d) For machines containing 5t CO2 ore more, the operator must keep a
record stating the quantity and type of refrigerant used, an quantities
added and that recovered during maintenance operations, repairs
and fi nal disposal ((EU) No. 517/2014 art. 6). .An example of this
record sheet can be downloaded from the site: www.polewr.com.
6.1 General instructions
!
Before any maintenance, make sure:
• the pneumatic circuit is no longer pressurized;
• the dryer is disconnected from the main power supply
Y
Always use the Manufacturer's original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunctioning.
Y
In case of refrigerant leakage, contact qualifi ed and authorized per-
sonnel.
Y
The Schrader valve must only be used in case of machine malfunc-
tion: otherwise any damage caused by incorrect refrigerant charging will
not be covered by the warranty.
6.2 Refrigerant.
Charging: any damage caused by incorrect refrigerant replacement car-
ried out by unauthorized personnel will not be covered by the warranty.
Z
Y
The equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R513A refrigerant is a colour-
less gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid accord-
ing to Directive PED 2014/68/EU)
GWP (Global Warming Potential) = 573.
!
In case of refrigerant leakage, ventilate the room.
PSE 460-1800
6.3 Preventive Maintenance Programme
To guarantee lasting maximum dryer effi ciency and reliability
Maintenance
Activity Description
(standard operating condi-
Activity
Check
Service
Check POWER ON indicator is lit.
Check control panel indicators.
Clean the fi lter of the water presso-
static valve, if it is not dirty increase
the inspection interval (see instruc-
tions) (PSE750-1800)
Check condensate drain.
Clean condenser fi ns.
Verify that the crankcase heater is
correctly positioned
Check electrical absorption.
Check refrigerant leaks.
Depressurize the dryer. Complete
drain maintenance.
Depressurize the dryer. Replace pre-
and post-fi lter elements.
Check
temperature
sensors.
Replace if necessary.
Dryer maintenance kit.
The following are available (see par. 8.4):
a) 3 years preventive maintenance kits;
b) service kit
• compressor kits;
• fan kits;
• hot gas valve kits;
• water condenser kits;
c) individual spare parts.
6.4 Dismantling
Maintenance Interval
The refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
tions)
The refrigerant fl uid is recovered before fi nal scrapping of the equipment
((EU) No. 517/2014 art.8).
structural work
exchanger
pipes/headers
drain
exchanger insulation
pipe insulation
compressor
condenser
refrigerant
valves
electrical cables
Z
%
Recycling Disposal
steel/epoxy-polyester resins
aluminium
copper/aluminium/carbon steel
polyamide
EPS (sintered polystyrene)
synthetic rubber
steel/copper/aluminium/oil
copper/aluminium
R513A
brass
copper/PVC
8/10

Publicité

loading

Ce manuel est également adapté pour:

Pse460Pse520Pse630Pse750Pse900Pse1200 ... Afficher tout