Télécharger Imprimer la page

Wilo -Control SC-L-FTS Serie Notice De Montage Et De Mise En Service page 34

Publicité

Les langues disponibles
  • FR

Les langues disponibles

English
6.3. Menu control and structure
6.3.1. Control
Fig. 3: Operation
The menu is controlled via the operating knob:
• Turn: Selection and set values
• Press: Change menu level or confi rm value
6.3.2. Set-up
The menu is divided into two areas:
• Easy menu
For quick commissioning using the factory set-
tings, only the operating mode and the activation
and deactivation values need to be set here.
• Expert menu
For display and setting of all parameters.
Open menu
1.
Press operating knob for 3 seconds.
2.
Menu item 1.0.0.0 appears.
3.
Turn operating knob to left: Easy menu
Turn operating knob to right: Expert menu
6.4. Initial commissioning
NOTE
Observe the installation and operating in-
structions for products provided on-site (level
sensors, connected consumers) as well as the
system documentation!
The following points must be checked before the
initial commissioning:
• Check the installation.
• All terminals must be retightened.
• Motor protection correctly set.
• The separate HAND-0-AUTO switch for each
pump must be set to "AUTO (A)". The factory
setting for these is "0 (OFF)"!
Switching on
1.
Turn main switch to ON position.
2.
The display lights up and outputs the latest
information.
3.
The "Standby" symbol appears and the switch-
gear is ready for operation. You can now set the
individual operating parameters.
NOTE
If the red fault LED lights up or fl ashes imme-
diately after activation, observe the error code
information on the display!
34
Fig. 4: Appearance of display
2
5
1 Control with standby pump
Current pump status: Number of registered pumps/
2
pump on/pump off
Display "FTS" for FTS mode
3 Current fi ll level
4 Unit of value currently displayed
5 Area for the display of graphical symbols
6.5. Setting the operating parameters
The menu is divided into seven areas:
1.
Control parameters (start/stop delays)
2.
Communication parameters (fi eld bus)
3.
Pump activation (activation and deactivation of
the connected pumps)
4.
Display of parameters currently set as well as data
for the switchgear (type, serial number etc.)
5.
Basic settings for the switchgear
6.
Fault memory
7.
Service menu (can only be activated by Wilo
customer service)
6.5.1. Menu structure
1.
Start the menu by pressing the operating knob
for 3 sec.
2.
Choose the selected menu: Easy or Expert.
3.
Follow the menu structure below for the desired
value and change this according to your specifi -
cations.
Menu 1: Control parameters
No.
Description
1.1.0.0 Operating mode
Display:
1.1.1.0
empty
1.2.0.0 Control values
1.2.2.0 Thresholds for on/off level
OPERATION AND FUNCTION
1
3
4
Display
WILO SE 08-2016 V05 DIN A4

Publicité

loading