OPERATION AND FUNCTION
Menu 1: Control parameters
No.
Description
Pump On
1.2.2.1
Value range: 0.09 to 12.45
Factory setting: 0.62
Pump Off
1.2.2.2
Value range: 0.06 to 12.42
Factory setting: 0.37
Delay times for activation and
1.2.5.0
deactivation of the pumps
Switch-off time delay
1.2.5.1
Value range: 0 to 60
Factory setting: 0
Stop delay at dry-running level
1.2.5.4
Value range: 0 to 10
Factory setting: 10
Activation delay time after dry
run
1.2.5.5
Value range: 0 to 10
Factory setting: 1
System activation delay time
after power interruption
1.2.5.6
Value range: 0 to 180
Factory setting: 0
Menu 2: Communication parameters
No.
Description
2.0.0.0 Communication
Field bus
Values: None, Modbus, BACnet,
2.1.0.0
GSM
Factory setting: None
Menu 3: Pump activation
No.
Description
3.0.0.0 Pump activation
Switching automatic mode on/
off
3.1.0.0
Values: ON, OFF
Factory setting: OFF
Menu 4: Display of current settings and basic switchgear
data
No.
Description
4.1.0.0 Current operating values
4.1.1.0 Current level
4.1.2.0 Current control values
4.1.2.1 Pump On
4.1.2.2 Pump Off
Installation and operating instructions Wilo-Control SC-L...-FTS
Menu 4: Display of current settings and basic switchgear
data
Display
No.
4.1.4.0 Limit values
4.1.4.1 Dry-running protection level
4.1.4.2 High water alarm level
4.2.0.0 Operating data
4.2.1.0 Total running time of the system
4.2.2.x Running time of the individual pumps
4.2.3.0 Unit switching cycles
4.2.4.x Switching cycles of the individual pumps
4.3.0.0 Details of switchgear
4.3.1.0 Switchgear type
4.3.2.0 Serial number (as ticker format)
4.3.3.0 Software version
4.3.4.0 Firmware version
Menu 5: Basic switchgear settings
No.
5.0.0.0 Basic settings
5.1.0.0 Communication
Display
5.1.1.0 Modbus
Baud rate
5.1.1.1
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
Slave address
5.1.1.2
Value range: 1 to 247
Factory setting: 10
Display
Parity
5.1.1.3
Values: even, non, odd
Factory setting: even
Stop bits
5.1.1.4
Values: 1, 2
Factory setting: 1
5.1.2.0 BACnet
Baud rate
5.1.2.1
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
Slave address
5.1.2.2
Value range: 1 to 255
Factory setting: 128
Description
Description
Display
English
35