Télécharger Imprimer la page

Lutron Grafik Eye PHPM-PA-DV-WH Instructions D'installation page 3

Publicité

Les langues disponibles

Les langues disponibles

Load Type Capability
Switching Power Module:
• Incandescent (tungsten)
• Halogen
• Magnetic low-voltage transformer (iron core)
• Electronic (solid-state) low-voltage transformer.
• Magnetic and electronic fluorescent lamp
ballasts
• Neon/cold-cathode
• HID
• Motor
- 1/2 HP at 277 V
- 1/3 HP at 120 V
Phase-Adaptive Power Module:
• Incandescent (tungsten)
• Halogen
• Magnetic low-voltage transformer (iron core)
• Electronic (solid-state) low-voltage transformer
• Lutron Tu-Wire
electronic fluorescent dimming
TM
ballast
• Neon/cold-cathode
3-Wire Fluorescent Power Module:
• Lutron Hi-Lume and Eco-10 (Eco Series) line-
voltage control electronic dimming ballasts
Product Compatibility
The following Lutron products may be used to
control these power modules:
• GRAFIK Eye QS control units
• GRAFIK Eye 3000 Series control units
• LP, LCP, GP dimming panels
• HomeWorks remote power panels
R
Test Load for Short-Circuit
• Turn power Off.
• Phase-Adaptive/Switching: Connect standard
switch between Hot/Live lead and the load wire
to test circuit.
• Fluorescent: Connect standard switch between
Hot/Live lead and the Dimmed Hot/Live and
switched Hot/Live leads of the ballast.
• Turn power On and check for short or open
circuits.
Hot/Live
Neutral
Phase-Adaptive/Switching
Hot/Live
Switch
Ballast
Neutral
Fluorescent
Switch
Load
Orange
Black/Brown
GRAFIK Eye
Power Modules
®
3

Publicité

loading