General Notes
Danger! Always turn OFF the circuit
breakers or remove the main fuses from
the power line before doing any work.
Failure to do so can result in serious
personal injury. More than one disconnect
may be required to de-energize this
device. Disconnect all power sources
before servicing unit.
• This power module must be installed by a
qualified electrician in accordance with all
applicable regulations.
• Improper wiring can result in personal injury,
damage to the interface, or damage to other
equipment.
• Up to three power modules per zone.
• The power module must be mounted with arrow
facing upward to ensure adequate cooling.
• CAUTION! Dimmed magnetic low-voltage
transformers: To avoid excessively high current
flow that can cause transformer overheating and
failure, observe the following:
(a) Do not operate the power module with all of
the lamps removed or with any lamps
inoperative.
(b) Replace any burned out lamps immediately.
(c) Use only transformers that incorporate
thermal protection or fused primary windings.
2
GRAFIK Eye
Power Modules
®
• Phase-Adaptive/Fluorescent: These power
modules contain circuitry that will shut down the
output if it is overloaded. To correct the problem,
turn off power and reduce the load to the
specified rating before re-applying power.
Note! Plastic faceplate must be installed on
module for normal operation (all models).