Télécharger Imprimer la page

Sovelor TITAN GAZ Manuel D'utilisation Et De Maintenance page 20

Publicité

Les langues disponibles

Les langues disponibles

properly insert the N gas seal:
• Locate the cable with 6-pin Wieland plug running out of the gas
valve group and insert the plug into the burner socket;
• Apply one of the two stickers with the serial number on the
nameplate of the machine characteristic data:
• Apply the second sticker with the serial number on the Assembly
and Installation Declaration contained in the user manual:
• The burner is not pre-adjusted by the manufacturer and must be
set
according
to
data
Characteristics of the user manual: follow the instructions in the
manual to complete the connection of the machine to the gas
supply system and for commissioning
Warning
Check all threaded connections on the gas line.
When commissioning, check for any gas leaks or
seepages using soap and water
4.5. CONNECTION TO FUEL SUPPLY
Warning
The heater must be installed, set up, and used in
compliance with all applicable regulations.
L-L 248.00-SO
N
reported
in
Table
of
Technical
EN
Warning
Before installing, check the gas supply conditions
required for the type of gas chosen and for the EU country
of installation (Tables I and II).
The gas supply pipe must be properly sized, conform to the installed
thermal power, and guarantee the necessary conditions for gas
supply.
Warning
The gas supply pressure must be guaranteed during
heater operation and not with the heater off.
The space heater has a gas ramp with: gas filter, pressure regulator,
safety electrovalve, work electrovalve, pressure stabilizer, pressure
valve.
It is good practice for the installer to set up the supply line as
follows:
1: filter-pressure regulator or filter
3: stopcock
Parts (1), (2) and (3) are available as accessories and are not
supplied with the heater.
When the line has been connected:
• Bleed the gas supply pipe;
• Check that the gas pipe is sealed.
• Open the gas stopcock and check the seal of all connections to
the heater.
4.6. CONNECTING BURNER TO "SNORKEL" DEVICE AND SETTING
COMBUSTION AIR
The burner air intake (3) can be connected outside the room to be
heated in order to suck in clean air and avoid depleting the oxygen
in the room.
The connection pipe must be rigid to prevent shrinking due to air
intake depression. It must have a minimum diameter of 100 mm and
maximum length of 6 metres.
Warning
If the hose is too long, remove the excess without leaving
loops and/or curves which may hinder air suction.
To connect the air pipe to the burner intake:
• remove burner box cover (a)
• remove burner box closure panel (b)
• insert air pipe (c) into the hole on closure panel (b) and fix it to
Snorkel intake (d) on the burner
• reassemble burner box cover (a) by sliding it along air pipe (c),
making sure that air pipe (c) does not detach from Snorkel intake
(d)
• fix panel (a) on the burner intake by turning it upside down so that
air pipe (c) is locked.
2: antivibration joint
4: gas ramp
43 / 88

Publicité

loading

Produits Connexes pour Sovelor TITAN GAZ