FMC-420RW-HSRRD
Notice
WARNING!
Risk of injury from electric shock. The system must be current-
free during connection work.
Product Description
Manual Call Point LSN improved resettable for outdoor use, surface
mounting. For installation refer to Page 5.
Connection
See Figure 3, Page 5.
Pos. Description
1
LSN1: a, b / LSN2: a, b
2
E
Address Setting
Look up the address in the tables (Pages 8 and 9) and set the 8 DIP switches
accordingly (see Pages 7).
Use always the same operating mode within one loop, stub or T-tap!
Address (A)
Operating mode
0
Loop/stub in LSN improved version mode with automatic
addressing
1 ... 254
Loop/stub/T-taps in LSN improved version mode with
manual addressing
255 = CL
Loop/stub in LSN classic mode (address range: max. 127)
Functional Test
1.
Press firmly onto the pane (6.1, Page 6). As soon as the alarm has been
triggered, the LED is illuminated and the color display of the pane turns
from white to red.
2.
To reset the manual call point, unlock the maintenance flap with the
test key and pull it forwards (6.2 and 6.3, Page 6).
3.
Insert the test key into the top openings and push it down (6.4, Page 6).
The color display turns white again.
4.
Close the maintenance flap (6.5, Page 6).
Technical Specifications
LSN operating voltage
LSN current consumption
Permissible operating temperature
Protection class (EN 60529)
Dimensions (H x W x D)
Bosch Sicherheitssysteme GmbH
Function
LSN incoming/LSN outgoing
Shielding
15 V DC to 33 V DC
0.4 mA
-25° C to +70° C
IP 67
108 x 108 x 66 mm
en
F.01U.099.400 | 1.0 | 2010.02
13