REFRIGERANT CONNECTIONS

POSITION OF THE UNITS

OUTDOOR UNIT AT A HIGHER LEvEL

L
Install a siphon on the Gas pipe every 5 m

OUTDOOR UNIT AT A LOWER LEvEL

L
The pipe links should have a minimum slope of
1/250 towards the outdoor unit.
models
H+ maxi
H- maxi
maximum length
H +
H -
125 - 125V
155 - 155V
185
50 m
50 m
50 m
50 m
50 m
50 m
L
L
On HEAT PUMP MODELS ONLY install a
siphon at the foot of the column (Gas pipe) for this
installation configuration.
405m
10 m
10 m
10 m
15 m
30 m
30 m
15
405M
H +
H -
205 - 255 - 305
405 - 505 - 605
755 - 905
15 m
25 m
15 m
15 m
30 m
30 m