1) Cut-off power supply.
2) Manually release the wings, move them to approx. half-stroke and lock them again.
3) Reset power supply.
4) Send a step-by-step control signal by pressing the button or the remote control key.
5) The wings should start an opening movement. If this is not the case, invert the movement wires of the
motor. (27<>28 for motor M1, and 24<>25 for motor M2) and the relevant limit switch inputs (10<>12 for
motor M1, and 11<>13 for motor M2).
6) Adjust Time, Operating Logic and Motor Power.
WARNING! This adjustment affects the safety of the automatic system.
Check that the thrust applied onto the wing complies with regulations in force.
The motor power can be adjusted by moving the special POWER trimmer.
TCA
The automatic closure time can be adjusted with this trimmer. Check Dip-switch DP1 N°5= On.
This function can be adjusted between 1 s minimum and 180 s maximum.
TRAC
It allows to adjust the delay time with which the gate second wing (MOTOR 1) starts closing.
Adjustment ranges from 0 s minimum to 40 s maximum.
TLAV
The maximum time of the opening and closing phases can be adjusted with this trimmer.
Time should be preset approx. 4 sec. longer than the actual stroke time of the automatic
system.
Adjustment ranges from 1 s minimum to 160 s maximum
POWER
The power of both motors can be adjusted with this trimmer.
DIP 1
The operating mode of "Pulsante P.P." (Step-by-step push button) and of the transmitter is
selected.
Off: operation: APRE > STOP > CHIUDE > STOP > (Open – Stop – Close – Stop)
On: operation : APRE > CHIUDE > APRE > (Open – Stop – Close – Stop)
DIP 2
Forewarning flashing light enabled or disabled.
Off: disabled forewarning flashing light.
On: enabled forewarning flashing light. The flashing light is activated 3 s before the motor starts.
DIP 3
Limit switches operating mode selection.
Off: when the opening/closing limit switches are triggered, the gate wing stops.
On: when the opening/closing limit switches are triggered, the gate wing starts slowing down.
See paragraphs "Speed and braking time"
DIP 4
Selection of Motor 2 delay time during opening (TRAP).
Off: 1 second
On: 2 seconds
DIP 5
The automatic closure is enabled or disabled.
Off: disabled automatic closure
On: enabled automatic closure
DIP 6
The multi-flat function is enabled or disabled.
Off: disabled multi-flat function.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse of the transmitter
have no effect in the opening phase.
DIP 7
Leave on OFF.
DIP 8
Activation of "water hammer".
Off: Disabled
On. Enabled. Before starting the gate opening movement, the gate is pushed further closed for
about 2 s, in order to facilitate the electric lock release.
DIP 9
Not in use.
DIP 10
To select the activation time of outputs "Courtesy light" and "Stair light".
Off: 120 seconds
On: 2 seconds
NOTE: All adjustment of Trimmers and Dip-switches should be carried out with motor stopped.
To check connections:
To adjust the motor power
Functions of Trimmers
Dip-switch DP1 functions
9