Nice RUN1800 Instructions Et Recommandations Pour L'installateur page 15

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 54
Input LED
Parameter
L6
Partial Open
L7
Maintenance
warning
L8
Fault list
Note: "
" represents the factory setting
Note (1): Automatically regulates the force required, maintaining a minimum guaranteed force level.
Note (2): Automatically regulates the force required.
All parameters can be adjusted as required without any contraindications, only the "Obstacle detection sensitivity" and "Motor force control"
may require special attention:
• Use of high force values are not recommended to compensate for the fact that the leaf has anomalous points of friction; excessive force
may impair the safety system and damage the leaf.
• If the "Obstacle detection sensitivity" is used in support of the system for impact force reduction, after each adjustment the force mea-
surement procedure must be performed, as envisaged by standard EN 12445.
• Wear and atmospheric conditions that influence movement of the gate; force settings should be checked periodically.
7.2.4) Level two programming (adjustable parameters)
The adjustable parameters are factory set as shown in the table 9, with: "
10. Follow the procedure carefully, as there is a maximum time of 10 seconds between pressing one key and another. If a longer period of
time lapses, the procedure will finish automatically and memorize the modifications made up to that stage.
Tabella 10: changing the adjustable parameters
1.
Press and hold key [Set] (approx. 3 s)
2.
Release the [Set] key when L1 LED starts flashing
3.
Press key [▲] or [▼] to move the flashing LED onto the input LED representing the parameter to
be changed
4.
Press the key [Set] and hold it down during step 5 and 6
5.
Wait approx. 3 seconds, after which the LED representing the current level of the parameter to be
modified will light up.
6.
Press key [▲] or [▼] to move the LED representing the parameter value.
7.
Release the key [Set]
8.
Wait 10 seconds before leaving the programme to allow the maximum time to lapse.
Note: Points 3 to 7 can be repeated during the same programming phase in order to set other parameters
Led (level)
L1
0,5 mt
L2
1 mt
L3
1,5 mt
L4
2 mt
L5
2,5 mt
L6
3 mt
L7
3,4 mt
L8
4 mt
L1
Automatic (based on seriousness of
manoeuvres)
L2
2.000
L3
4.000
L4
7.000
L5
10.000
L6
15.000
L7
20.000
L8
30.000
L1
Manoeuvre 1 result (most recent)
L2
Manoeuvre 2 result
L3
Manoeuvre 3 result
L4
Manoeuvre 4 result
L5
Manoeuvre 5 result
L6
Manoeuvre 6 result
L7
Manoeuvre 7 result
L8
Manoeuvre 8 result
Value
The measurement of the partial opening. Par-
tial opening can be controlled with the 2nd
radio command or with "CLOSE", if the "Clo-
se" function is present, this becomes "Partial
open".
Adjusts the number of manoeuvres after
which it signals the maintenance request of
the automation (see paragraph "7.4.4 Main-
tenance warning").
The type of defect that has occurred in the
last 8 manoeuvres can be established (see
paragraph "7.6.1 Malfunctions archive").
" However, they can be changed at any time as shown in Table
Description
Example
SET
3s
L1
SET
or
SET
or
SET
10s
15
GB

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Run1800pRun2500Run2500p

Table des Matières