PARAMETERS
0 = off
14
DEAD MAN
1 = on (safety devices disabled)
0 = deactivated
1 = gate open light ON/OFF
2 = gate open light proportional
3 = electric lock for partial gate *
GATE OPEN
4 = electric lock for partial gate with relay
15
INDICATOR
interface **
5 = Traffic light When open COM/IND activated
and COM/ELEC deactivated (GREEN)
Not open COM/IND deactivated and COM/ELEC
activated (RED)
16
MAINTENANCE
Service interval cycle threshold
Enabling of continuous flashing when service is
MAINTENANCE
required (only active with gate closed).
17
FLASH
0 = off
1 = on
0 = magnetic electrolock. Output works only
when the gate is closed. We recommend to set
ELECTROLOCK
18
the pre-flash to 2 seconds ****
ACTIVATION
Activated for from 1 to 20 seconds when the
motors start to open the gate
From motor M1 closed
WATER
0 = off
19
HAMMERING IN
Motor M1 activated for from 1 to 30 seconds in
OPENING
the closing direction to ensure that the electric
lock releases
From motor M1 closed
WATER
0 = off
20
HAMMERING IN
Motor M1 activated for from 1 to 30 seconds in
CLOSING
the closing direction to ensure that the electric
lock engages
Motor release from limit switch. Useful for
lightweight gates
MOTOR RELEASE
21
0 = off
AT STOP
1 to 10 release levels (1 = minimum release, 10
= maximum release)
High-speed motor start-up. Useful for heavy
gates in winter
START UP BOOST
22
0 = off
(NO FASTLINE)
1 = on
2 = maximum
Leaf 1 closing delay with gate open
CLOSING DELAY
23
0 = Off
M 1
1 = 1 to 180 Seconds On
ENCODER
1 = Off (use of virtual encoder)
24
(NO FASTLINE)
2 = On (use of motor's physical encoder)
ENCODER
1 to 10 pulses per revolution of the physical
25
PULSES
encoder (only with 24 set as "2")
(NO FASTLINE)
0 = Circuit board inputs active
1 = SBS-CLOSE-OPEN-PAR circuit board
inputs deactivated
CIRCUIT BOARD
26
WARNING! If the parameter is set as 1, the
INPUT LOCKING
control unit will request a 4-figure numerical
password, which will have to be entered again
to return the parameter to 0
27
DEFAULT
Restoring the default values
* The OPEN command from the transmitter and the 14A control unit will activate the parcial gate electric lock when the parameter is set on 3 or
4. The activation time is as set in parameter 18
** If the setting is 4, the GATE OPEN WARNING LIGHT output must be connected to the coil of a relay (24 Vdc coil). Interface the relay contact
with the electric lock
*** For RÉVO motors, DEFAULT = 2
**** Gate closed = output activated; Gate not closed = output deactivated
DESCRIPTION
DEFAULT
MIN.
0
0
0
0
10
1
0
0
2
0
0
0
0
0
0 ***
0
0
0
1
0
1
1
1
1
0
0
0
0
EN
MAX.
UNIT
1
5
x 1000
200
cycles
1
20
s
30
s
30
s
10
2
180
s
2
10
1
1
31