5. Function settings (continued)
No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-E.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
36
-
-
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-E.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
37
-
-
No.38
CO
concentration display setting
2
Set to display CO
concentration when the CO
2
PZ-70CSW-E) is used.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
38
-
-
- This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-E.
- When displaying CO
concentration, supply air temperature cannot
2
be displayed simultaneously.
- CO
concentration display shows the value detected by a CO
2
sensor connected to Lossnay unit. The value may differ from the
actual indoor CO
concentration. This function cannot be used as a
2
measuring instrument.
- The value may significantly differ from the actual indoor CO
concentration for approx. 15 minutes after starting operation.
- When 3rd party's CO
sensor is connected, CO
2
not displayed on PZ-62DR-E screen.
Calculated supply air temperature display
No.39
setting
Set to display calculated supply air temperature or not.
This function is N/A from Lossnay unit DIP-SW.
In addition, this function is available only when "Sensor value" is set
to "Yes"(Display) by the remote controller PZ-62DR-E.
CO
concentration and supply air temperature can not be displayed
2
at the same time.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
39
-
-
- CO
concentration and supply air temperature can not be displayed
2
at the same time.
Setting
Outdoor temperature
check
display
0
N/A
Available on the screen
1
(Factory setting)
of PZ-62DR-E
Setting
Indoor temperature
check
display
0
N/A
Available on the screen
1
(Factory setting)
of PZ-62DR-E
sensor (PZ-70CSB-E,
2
Setting
CO
concentration
2
check
display
0
N/A
Available on the screen
1
(Factory setting)
of PZ-62DR-E
2
concentration is
2
Setting
Calculated supply air
check
temperature display
0
N/A
(Factory setting)
Available on the screen
1
of PZ-62DR-E
No.40, 41
Set the 10 digit of temperature exchange efficiency which is used to
calculate supply air temperature.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
SW No.
Setting
-
-
-
-
-
N/A
-
-
-
-
-
DIP-SW
Setting
SW No.
Setting
-
-
-
-
N/A
-
-
-
-
-
-
No.42
Outdoor temperature correction
Set the correction for the outdoor temperature displayed on the
PZ-62DR-E screen by function
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
SW No.
Setting
-
-
-
-
-
2
-
-
N/A
-
-
-
-
-
-
-
-
Eng-20
Temperature exchange efficiency
setting
PZ-62DR-E
Setting
check
check
Function No. Setting Data
-
0
-
1
-
2
-
3
-
4
-
40
5
-
6
7
-
(Factory setting)
-
8
-
9
PZ-62DR-E
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
-
1
-
2
-
3
-
41
4
-
5
-
6
-
7
-
8
-
9
.
No. 36
PZ-62DR-E
Setting
check
check
Function No. Setting Data
-
0
-
1
-
2
-
3
-
4
-
5
-
6
7
-
42
(Factory setting)
-
8
-
9
-
10
-
11
-
12
-
13
-
14
10 digit of temperature
exchange efficiency
0
1
2
3
4
5
6
7
8
9
1 digit of temperature
exchange efficiency
0
1
2
3
4
5
6
7
8
9
The correction to
thermistor detection
-7 K (-12.6 °F/-7 °C )
-6 K (-10.8 °F/-6 °C )
-5 K (-9 °F/-5 °C )
-4 K (-7.2 °F/-4 °C )
-3 K (-5.4 °F/-3 °C )
-2 K (-3.6 °F/-2 °C )
-1 K (-1.8 °F/-1 °C )
0 K (0 °F/0 °C )
+1 K (+1.8 °F/+1 °C )
+2 K (+3.6 °F/+2 °C )
+3 K (+5.4 °F/+3 °C )
+4 K (+7.2 °F/+4 °C )
+5 K (+9 °F/+5 °C )
+6 K (+10.8 °F/+6 °C )
+7 K (+12.6 °F/+7 °C )