6. Check points after installation work

After installation work has been completed, check the following points once again.
If any failure is detected, be sure to fix it.
Check the following points before trial operation, and place a check mark
(1) Check points - Main unit installation work
The duct connecting flanges are securely attached by using the supplied screws.
The length of 3.3 ft. (1.0 m) or more (for LGH-F300, F380RVX2-E)/8.2 ft (2.5 m) or more (for
LGH-F470, F600RVX2-E)/9.8 ft (3 m) or more (for LGH-F940, F1200RVX2-E) is provided for the
outdoor side ducts (OA, EA) from a building wall surface.
A downward gradient of 1/30 or more toward a building wall is provided for the outdoor side
ducts (OA, EA).
The two outdoor side ducts (OA, EA) are covered with a heat-insulating material.
(2) Check points - Wiring work
A combination of power supply voltage, model name, and remote controller is correct.
The wires are correctly connected according to the wire connection diagram.
The wires are securely connected to the terminal blocks.
The wires are securely fixed.
The connectors on the circuit board are securely connected.
The grounding cable is installed.
The cables are correctly fixed by using the cord clips and cable glands.
In terms of size and specification, the proper power supply cable and transmission cables are used. 4.3 Electrical installation
(3) Check points - Function setting
The "Main" Lossnay is correctly set.
The address setting switches (SW11, SW12) are correctly set.
The function selection switches (SW2, SW5) are correctly set.
The function settings by the remote controller are correct.
(For details, refer to the Installation Manual of the remote controller PZ-62DR-E.)
To prevent early failures, be sure to check the check points after installation work.
in the corresponding check box.
Eng-28
Reference page
4.1 Hanging the Lossnay unit
3. Standard installation examples
4.2 Duct works
3. Standard installation examples
4.2 Duct works
4. Installation method
4.3 Electrical installation
4.3 Electrical installation
4.3 Electrical installation
4.3 Electrical installation
4.3 Electrical installation
4.3 Electrical installation
4.3 Electrical installation
5. Function settings
5. Function settings
5. Function settings
5. Function settings