5. Function settings (continued)
Auto fan speed setting without Lossnay or
M-NET system controller
When CO
sensor is connected but any remote controller is not
2
connected, SW 5-9 has to be ON in order to operate according to
CO
concentration.
2
When SW 5-9 is ON, any Lossnay remote controller or M-NET
system controller can not be connected and not possible to interlock
with City Multi or Mr. Slim unit.
DIP-SW
Setting
Auto fan speed setting without Lossnay or M-NET
check
system controller
SW No.
Setting
OFF
N/A
(Factory setting)
SW5-9
ON
Fan speed changes according to CO
Filter maintenance and fan power up
No. 1
setting against filter choking
Set the schedule for filter cleaning based on the estimated
concentration of dust in the air.
When fan power up is available, exhaust and supply fans power up at
1,000 hrs, 2,000 hrs and 3,000 hrs gradually.
If function
or
is already worked, fan power up function
No. 55
No. 56
may not be available.
Estimated hour differs by actual operated fan speed.
This function is N/A from Lossnay unit DIP-SW.
The target interval can be selected at
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
1
-
-
-
-
CAUTION
• When the cumulative operation time of the Lossnay exceeded
the estimated hours, the maintenance icon will appear on
the air conditioner remote controller or the Lossnay remote
controller. After cleaning the filter, the maintenance icon can be
reset. Refer to the Instruction book for the remote controller.
No.2
Lossnay core maintenance indicator setting
When using PZ-62DR-E, set to enable Lossnay core maintenance
display. Estimated hour differs by actual operated fan speed.
This function is N/A from Lossnay unit DIP-SW.
The target interval can be selected at
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
2
-
-
CAUTION
• When the cumulative operation time of the Lossnay exceeded
the estimated hours, the maintenance icon will appear on the
Lossnay remote controller. After cleaning the Lossnay core, the
maintenance icon can be reset. Refer to the Instruction book for
the remote controller.
concentration
2
.
No. 83
No. 84
,
Setting
Filter maintenance
check
indicator
0
N/A
(Factory setting)
Appears at the
1
interval of estimated
3,000 hrs
Appears at the
2
interval of estimated
3,000 hrs
3
N/A
No. 85
No. 86
.
,
Setting
Lossnay core
check
maintenance indicator
0
N/A
(Factory setting)
Indicate at estimated
1
6,000 hrs
Automatic recovery setting after power
No.5
interruption
Sets for automatic recovery following power interruption.
DIP-SW
Setting
SW No.
Setting
-
OFF
(Factory setting)
SW2-8
-
ON
* If a power failure happens when Lossnay is operating by external
signal via TM2 12 or YZ, Lossnay returns the condition before power
failure regardless of the external input condition after power recovery.
No. 6
Indoor negative pressure setting
Exhaust fan speed becomes
bigger than supply fan speed.
Remote controller indicates fan
speed of exhaust fan.
DIP-SW
Setting
SW No.
Setting
Fan power
UP
-
N/A
OFF
(Factory setting)
SW2-4
N/A
ON
-
Available
Available
No.7
Indoor positive pressure setting
Supply fan speed becomes bigger
than exhaust fan speed.
Remote controller indicates fan
speed of supply fan.
DIP-SW
Setting
SW No.
Setting
-
OFF
(Factory setting)
SW2-5
ON
-
Max. fan speed setting during the first 30
No.8
minutes
This sets the fan to run forcibly for 30 minutes when operation starts to
ventilate the indoor area. After 30 minutes, fan speed can be changed.
Use this setting if the indoor air is contaminated at night when the
system is shut down and you desire to ventilate the indoor area
quickly when operation is started in the morning.
This function is N/A from Lossnay unit DIP-SW.
While this function is working,
on the screen of PZ-62DR-E.
DIP-SW
Setting
SW No.
Setting
-
N/A
-
Eng-17
PZ-62DR-E
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
1
5
-
2
3
Fan speed
Display
4
3
2
1
PZ-62DR-E
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
1
6
2
-
3
Fan speed
Display
4
3
2
1
PZ-62DR-E
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
1
7
2
-
3
and selected fan speed are displayed
PZ-62DR-E
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
8
-
1
Lossnay operation when
the power is recovered
DIP-SW priority
Lossnay remains stopped.
Lossnay starts operation.
Lossnay returns to the
state before interruption*
Supply fan
Exhaust
fan
1 down 2 down
4
3
2
3
2
1
2
1
1
1
1
1
Down level of supply fan
speed
DIP-SW priority
N/A
Supply fan speed is 1
down to exhaust fan speed
Supply fan speed is 2
down to exhaust fan speed
Exhaust fan
Supply
fan
1 down 2 down
4
3
2
3
2
1
2
1
1
1
1
1
Down level of exhaust
fan speed
DIP-SW priority
N/A
Exhaust fan speed is 1
down to supply fan speed
Exhaust fan speed is 2
down to supply fan speed
Max. fan speed setting
during the first 30 minutes
N/A
Available