4. Installation method (continued)
• Install the duct heater separated from the product by a
distance of 2.2 yd (2 m) or more.
Failure to do so may result in equipment damage due to the
transmission of residual heat from the heater.
• Ensure that the duct heater and Lossnay are wired and that
the Lossnay function settings have been configured, and then
always check operation by trial operation.
• For the duct heater output, see function setting
No. 61
.
When using After-heater output signal, the wiring should be as shown
by the following picture.
Lossnay
OA
Power Supply
for heater
For the heater, observe the cautions listed in Pre-heater.
5
When switching fan speed externally
(when a sensor or other equipment is connected)
Using a field supply sensor, etc., make connection by inserting the
optional remote controller adapter (PAC-SA88HA-E or PAC-725AD)
in the connector CN17 (Red) as shown by the figure.
Lossnay will operate at the fan speed following the table below,
regardless of the remote controller setting.
CN17 (Red)
Fan speed
1-2 (Brown-Red)
1-3 (Brown-Orange)
1-4 (Brown-Yellow)
1-5 (Brown-Green)
n Example "Fan speed 4"
Remote controller adapter
(Optional) PAC-SA88HA-E
Field supply sensor, etc.
or PAC-725AD
SW1
Not used. Insulate completely.
Max wiring length 11 yd (10 m)
Use this in such a way that it ventilates at low fan speed normally,
and when the external sensor detects contamination of indoor air, or
SW1 is on, it changes to high fan speed operation.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputted into main unit referring to 3.
Cannot be used in conjunction with the following functions:
- To change fan speed by 0 - 10 VDC input.
- Connecting CO
sensor PZ-70CSB-E or PZ-70CSW-E.
2
No. 60
2.2 yd (2 m) or more
SA
TM3
9
Relay
10
Max. 230 VAC, 1 A
24 VDC, 1 A
Min. 208 VAC, 100 mA
5 VDC, 100 mA
Power Supply
for relay
4
3
2
1
Lossnay
control board
Brown 1
CN17
Red 2
Orange 3
Yellow 4
Green 5
Fan speed
selection
6
When switching By-pass externally.
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E or PAC-725AD) in the connector
CN26 (White).
and
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
With SW1 is "ON", the ventilation mode of Lossnay is changed to the
By-pass ventilation regardless of the setting on the remote controller.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputted into main unit referring to 3.
* When the outdoor air temperature drops lower than 46˚F (8˚C), it
changes to the heat recovery ventilation. (In this case, ventilation
mode icon on the display of the remote controller does not change
from the previous mode, it might be different from the actual unit
operation.)
7
To change fan speed by 0 - 10 VDC input
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E or PAC-725AD) in the connector
CN26 (White).
Not used. Insulate
completely.
e.g. 3rd party CO
To change fan speed by 0 - 10 VDC input, the wiring should be as
shown by the above picture. Refer to function settings
more details.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputed into main unit referring to 3.
Cannot be used in conjunction with the following functions:
- Switching fan speed externally (CN17).
- Connecting CO
CAUTION
• Make sure of correct polarity.
• Do not apply voltages higher than 10 VDC.
Eng-11
Remote controller adapter
(Optional) PAC-SA88HA-E
or PAC-725AD
Brown 1
Red 2
SW1
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 11 yd (10 m)
Remote controller adapter
Lossnay
(Optional) PAC-SA88HA-E
control board
or PAC-725AD
Brown 1
CN26
Red 2
Orange 3
Yellow 4 (0 - 10 VDC)
External
Fan speed/
Green 5 (COM)
device
Ventilation
mode selection
sensor
Max wiring length 11 yd (10 m)
2
sensor PZ-70CSB-E or PZ-70CSW-E.
2
Lossnay
control board
CN26
Fan speed/
Ventilation
mode selection
for