FloTech Programmable Retain / Overfill Monitor
Cable Installation Instructions
FloTech recommends you use FT401 jacketed 7-conductor
cable when wiring a new system. This cable is specially
designed to be oil, UV, and abrasion resistant. It incorporates a
noble tin-plated stranded copper wire which resists corrosion.
When installed properly, this cable will provide years of reliable
service.
See the Proper Wire Connections section for more detailed
directions about stripping and terminating the cables.
Monitor Housing
After the monitor housing is mounted, install FloTech FT402
cable glands in the openings where needed. These are, as
illustrated in Fig 3. : Power, Overfill Sensors, Retain Sensors (if
equipped) and Socket. Route the lengths of FloTech FT401
cable through the conduit openings. Cut the cables to length
leaving approximately 8 inches of extra length inside the
monitor housing.
Unused conduit openings in the sensor housings must have a ½
inch NPT pipe plug installed. Note that when using the
FloTech FT390 Dual Socket Assembly, you only need to install
one cable gland for the socket wiring.
Fig. 3
Monitor Housing Cable Routing Diagram
10464 REV C
7