FloTech Programmable Retain / Overfill Monitor
System powers up and runs through power on
test sequence OK, then flashes all sensor
LEDs in an alternating pattern:
This means that the monitor is not programmed.
1. Go to the PROGRAMMING section of this manual and
program the monitor.
2. If the monitor fails to program, call FloTech for
Technical Service.
System will not load and one or more RED
sensor LEDs are lit on inactive sensor inputs:
Follow these instructions for top or bottom sensors.
1. Remove onboard monitor cover.
2. Check the sensor inputs on TB2 that are not being used
(inactive sensor inputs). Make sure there are no wires
connected.
3. Go to the PROGRAMMING section of this manual and
repeat this procedure, making certain to accurately
program the unit.
4. If the monitor still does not function properly, contact
FloTech Technical Service for further instructions.
System will not load and one or more RED
sensor LEDs are lit on active sensor inputs:
Follow these instructions for top or bottom sensors.
1. Remove onboard monitor cover.
2. Go to TB2. Remove sensor wire from the terminal
block that corresponds with the lit LED. Example: If
LED TOP #3 is lit, remove the sensor wire to terminal
T3 (yellow).
3. Select a compartment where the LED is NOT lit and
exchange that wire with the suspect wire. Example:
18
10464 REV C