3. MAIN APPLICATIONS - BREAKERS (ENERGIZED)
d. Scan each breaker/fuse – the order of scanning does not matter. You can scan each
breaker/fuse multiple times. The receiver is recording the highest detected signal.
Usage tip: For best results try to scan at the output of the breaker/fuse.
Figure 3.4b
SCAN mode –
receiver scanning breaker/fuse
2
4. Step 2 -
LOCATE
a. Select LOCATE mode by using the directional arrows to
highlight this operating mode and pressing the yellow
"ENTER" button. (See figure 3.4c)
b. Rescan each breaker/fuse by touching each with the Tip
Sensor for a half second. Active red arrow indicates scanning
process (see Figure 3.4c). Make sure the groove on the Tip
Sensor is parallel to the breaker lengthwise. (See Figure 3.4d)
Usage Tip: Hold receiver in the same position as during
scanning step (step 3.4a-d).
c. Rescan all breakers/fuses until solid green arrow and audible alert (continuous beep)
indicates that the correct breaker/fuse was found. (See figure 3.4e)
d. Press ENTER when complete to return to Home screen.
Usage Tip: The accuracy of breaker/fuse identification results can be verified by switching
the receiver to Energized TIP SENSOR mode and checking that that the signal level of the
breaker identified by the receiver is the highest among all breakers.
Figure 3.4c
LOCATE mode –
receiver checking breaker/fuse
Figure 3.3e
LOCATE mode – receiver identified breaker
Usage tip:
To assure detection accuracy, when the correct
breaker/fuse is indicated, continue locating
remaining breakers on the panel to verify that
signal is not present in any other breaker/fuse.
19
Figure 3.4d